2.11.1.3 Telephone as Alternative to Emergency Doors
Go To Full Code Chapter
Where an elevator is installed in a single blind hoistway and there are no landings from which to gain access through an emergency door, a means of two-way conversation conforming to 2.27.1.1.4 shall be provided.
NOTE: Examples are pulp mills, grain elevators, dams, and similar locations.