1224.5.3.1 Number
There shall be a minimum of one technology distribution room on each floor of the facility.

Exception: For existing facilities not undergoing major renovation, a technology distribution room may serve adjacent floors.
1224.5.3.2 Size
  1. Technology distribution rooms shall be sized based on the area of the floor being served, with minimum clear dimensions as follows:

    Area Served in
    Square Feet (m2)
    Minimum Technology
    Distribution Room Size
    ≤ 8,000 square feet
    (740 m2)
    10 feet by 10 feet
    (3.05 m by 3.05 m)
    8,001 — 15,000 square feet
    (1400 m2)
    10 feet by 12 feet
    (3.05 m by 3.66 m)
    15,001 — 25,000 square feet
    (2325 m2)
    10 feet by 14 feet
    (3.05 m by 4.27 m)
    > 25,000 square feet
    (2325 m2)
    12 feet by 14 feet
    (3.66 m by 4.27 m)
  2. Where ceilings are provided, the minimum clear height shall be 9 feet (2.75 m).

    Exception: Existing buildings shall be permitted to have a minimum clear height of 8 feet (2.44 m).
1224.5.3.3 Location
Technology distribution rooms shall be provided throughout the facility as necessary to meet the maximum cable distance requirement for the cabling system specified.

Related Code Sections

1224.5.3 Interior Environment, Technology Distribution Room
There shall be a minimum of one technology distribution room on each floor of the facility. Exception: For existing facilities not undergoing ...
1224.5.3 Interior Environment, Technology Distribution Room
There shall be a minimum of one technology distribution room on each floor of the facility. Exception: For existing facilities not undergoing major ...
1224.5.3 Interior Environment, Technology Distribution Room
There shall be a minimum of one technology distribution room on each floor of the facility. Exception: For existing facilities not undergoing ...
1224.5.3.2 Interior Environment, Size
Technology distribution rooms shall be sized based on the area of the floor being served, with minimum clear dimensions as follows: Area Served ...
1224.5.3.1 Interior Environment, Number
There shall be a minimum of one technology distribution room on each floor of the facility. Exception: For existing facilities not undergoing ...