// CODE SNIPPET
A509.4.2 Target Displacement (δt)
JUMP TO FULL CODE CHAPTER
The target displacement of the control node (typically the center of mass of the building's roof) shall be determined using the following equation:

where:
TABLE A509.4.2 VALUES OF MODIFICATION FACTOR, C0

where:
C0 = | Modification factor to relate spectral displacement to expected building roof displacement. Value of C0 can be estimated using any one of the following: | |
1. | The first modal participation factor at the level of the control node. | |
2. | The modal participation factor at the level of the control node computed using a shape vector corresponding to the deflected shape of the building at the target displacement. | |
3. | The appropriate value from Table A509.4.2. |
TABLE A509.4.2 VALUES OF MODIFICATION FACTOR, C0
NUMBER OF STORIES | C0 |
1 | 1.0 |
2 | 1.2 |
3 | 1.3 |
5 | 1.4 |
10+ | 1.5 |
NOTE: Linear interpolation shall be used to calculate intermediate values. | |||||
C1 | = | Modification factor to relate expected maximum inelastic displacements to displacements for linear elastic response. C1 shall not be taken as less than 1.0. | |||
= | 1.0 for Te ≥ T0 | ||||
= | [1.0 + (R - 1)T0/Te]/R for Te < T0 | ||||
Where: | |||||
R | = | Strength ratio = | ![]() | ||
Vy | = | Yield strength calculated using the results of static pushover analysis where the nonlinear base-shear roof-displacement curve of the building is characterized by a bilinear relation (see Section A509.4.5). | |||
T0 | = | Characteristic period of the response spectrum, defined as the period associated with the transition from the constant acceleration segment of the spectrum to the constant velocity segment of the spectrum. | |||
C2 | = | Modification factor to represent the effect of hysteresis shape on maximum displacement response. | |||
= | 1.3 where T > T0 | ||||
= | 1.1 where T ≥ T0 | ||||
Exception: Where the stiffness of the structural component in a lateral-force-resisting system, which resists no less than 30 percent of the story shear, does not deteriorate at the target displacement level, C2 may be assumed to be equal to 1.0. | |||||
Sa | = | Response spectral acceleration at the effective fundamental period and damping ratio of the building, g, in the direction under consideration. | |||
Te | = | Effective fundamental period of the building in the direction under consideration, per Section A509.4.5. |
Related Code Sections
A509.4.2 Earthquake Hazard Reduction in Existing Concrete Buildings and Concrete With Masonry Infill Buildings, Target Displacement (δt)
The target displacement of the control node (typically the center of mass of the building's roof) shall be determined using the following equation ...
2010 Existing Building Code of NY > A5 Earthquake Hazard Reduction in Existing Concrete Buildings and Concrete With Masonry Infill Buildings > A509 Tier 3 Analysis Procedure > A509.4 Displacement Coefficient Analysis Procedure > A509.4.2 Target Displacement (δt)
24.7.2* Emergency Communications Systems (ECS), Targeted Recipients
The DRMNS shall be capable of sending alert messages to target recipients ...
National Fire Alarm and Signaling Code 2016 of New York State > 24 Emergency Communications Systems (ECS) > 24.7* Distributed Recipient Mass Notification Systems (DRMNS) > 24.7.2* Targeted Recipients
A509.4.1 Earthquake Hazard Reduction in Existing Concrete Buildings and Concrete With Masonry Infill Buildings, General
with Section A509.1. The general procedure for execution of the displacement coefficient analysis shall be determined in accordance with Section A509.4.5 ...
2010 Existing Building Code of NY > A5 Earthquake Hazard Reduction in Existing Concrete Buildings and Concrete With Masonry Infill Buildings > A509 Tier 3 Analysis Procedure > A509.4 Displacement Coefficient Analysis Procedure > A509.4.1 General
3404.3.3.5.2 Flammable and Combustible Liquids, Displacement Protection
Shelves shall be of sufficient depth and provided with a lip or guard to prevent individual containers from being displaced.
Exception:
Shelves ...
2010 Fire Code of NY > 34 Flammable and Combustible Liquids > 3404 Storage > 3404.3 Container and Portable Tank Storage > 3404.3.3 Indoor Storage > 3404.3.3.5 Shelf Storage > 3404.3.3.5.2 Displacement Protection
5704.3.3.5.2 Flammable and Combustible Liquids, Displacement Protection
Shelves shall be of sufficient depth and provided with a lip or guard to prevent individual containers from being displaced. Exception: Shelves ...
Fire Code 2015 of New York State > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.3 Container and Portable Tank Storage > 5704.3.3 Indoor Storage > 5704.3.3.5 Shelf Storage > 5704.3.3.5.2 Displacement Protection