1910.106(b)(2)(viii)(a) [Reserved]
1910.106(b)(2)(viii)(b) [Reserved]
1910.106(b)(2)(viii)(c) [Reserved]
1910.106(b)(2)(viii)(d)
Openings for gaging shall be provided with a vaportight cap or cover.
1910.106(b)(2)(viii)(e)
For Category 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), other than crude oils, gasolines, and asphalts, the fill pipe shall be so designed and installed as to minimize the possibility of generating static electricity. A fill pipe entering the top of a tank shall terminate within 6 inches of the bottom of the tank and shall be installed to avoid excessive vibration.
1910.106(b)(2)(viii)(f)
Filling and emptying connections which are made and broken shall be located outside of buildings at a location free from any source of ignition and not less than 5 feet away from any building opening. Such connection shall be closed and liquidtight when not in use. The connection shall be properly identified.

Related Code Sections

1910.106(b)(2) Hazardous Materials, Installation of Outside Aboveground Tanks
1,000 gallons capacity containing other than Category 1 flammable liquids may have open vents. (See paragraph (b)(2)(vi)(b) of this section ...