42.7.2.2.1
Delivery operations shall meet all applicable requirements of NFPA 385 and the requirements of 42.7.2.2.2 through 42.7.2.2.6. [30A:9.2.2.1]
42.7.2.2.2
No separation shall be required between the delivery vehicle and the fill connection of an underground storage tank. [30A:9.2.2.2]
42.7.2.2.3
The delivery vehicle shall be separated from any aboveground tank in accordance with Table 42.7.2.2.3. [30A:9.2.2.3]
Table 42.7.2.2.3 Minimum Separation Distances Between Delivery Vehicles and Aboveground Tanks
Separation Distance Between
Delivery Vehicle and
Aboveground Tank
(ft)
Protected aboveground tanks
0
Tanks in abovegrade vaults
(measured from vault wall)
0
Tanks filled by gravity
0
Fire-resistant tanks
15
Other tanks meeting the
requirements of NFPA 30
storing Class II or Class III liquids
15
Other tanks meeting the
requirements of NFPA 30
storing Class I liquids
25
[30A:Table 9.2.2.3]
42.7.2.2.3.1
Separation distances shall be imposed by the use of curbing, guard posts, or other approved methods. [30A:9.2.2.3.1]
42.7.2.2.3.2*
Means shall be provided to prevent an accidental release originating from the delivery vehicle from flowing under the aboveground tank. [30A:9.2.2.3.2]
42.7.2.2.4 Delivery Vehicle Location
42.7.2.2.4.1
The delivery vehicle shall be located so that all parts of the vehicle are on the premises when delivery is made. [30A:9.2.2.4.1]
42.7.2.2.4.2
Where fuel dispensing facilities are located inside buildings, the fuel delivery vehicle shall be permitted to be located off premises at approved locations. [30A:9.2.2.4.2]
42.7.2.2.4.3
Existing fuel dispensing facilities shall not be required to meet 42.7.2.2.4.1. [30A:9.2.2.4.3]
42.7.2.2.5
Tank filling shall not begin until the delivery operator has determined that the tank has sufficient available capacity (i.e., ullage). [30A:9.2.2.5]
42.7.2.2.6
Tanks shall be filled through a liquidtight connection. [30A:9.2.2.6]
42.7.2.2.6.1
Where an aboveground tank is filled by means of fixed piping, either a check valve and shutoff valve with a quick-connect coupling or a check valve with a dry-break coupling shall be installed in the piping at a point where connection and disconnection is made between the tank and the delivery vehicle. This device shall be protected from tampering and physical damage. [30A:9.2.2.6.1]
42.7.2.2.6.2
Underground tanks and tanks in belowgrade vaults shall be filled through a liquidtight connection within a spill container. [30A:9.2.2.6.2]

Related Code Sections

42.7.2.2 Refueling, Tank Filling and Bulk Delivery
] Tank filling shall not begin until the delivery operator has determined that the tank has sufficient available capacity (i.e ...
42.7.2.2.5 Refueling,
Tank filling shall not begin until the delivery operator has determined that the tank has sufficient available capacity (i.e., ullage). [30A:9.2.2.5] ...
42.7.2.2.5 Refueling,
Tank filling shall not begin until the delivery operator has determined that the tank has sufficient available capacity (i.e., ullage). [30A:9.2.2.5] ...
42.7.2.2.4 Refueling,
The delivery vehicle shall be located so that all parts of the vehicle are on the premises when delivery is made. Exception: This requirement shall ...