3404.1.2 Tank Capacity Limitations
JUMP TO FULL CODE CHAPTER
Except at a bulk plant or terminal or as otherwise specified in this chapter, the capacity of flammable and combustible liquid storage tanks shall not exceed the amounts set forth in FC 3404.1.2.1 through 3404.1.2.4.
Individual underground flammable liquid storage tanks shall not exceed a capacity of 4,000 gallons (15 140 L). The aggregate capacity of underground flammable liquid storage tanks at a premises shall not exceed 20,000 gallons (75 700 L).
Individual underground combustible liquid storage tanks shall not exceed a capacity of 12,000 gallons (45 420 L). The aggregate capacity of underground combustible liquid storage tanks at a premises shall not exceed 40,000 gallons (151 400 L).
The aggregate capacity of aboveground combustible liquid tanks installed outdoors at a premises shall not exceed 30,000 gallons (113 550 L).
The aggregate capacity of aboveground combustible liquid tanks installed indoors shall not exceed 20,000 gallons (75 700 L).
Related Code Sections
1305.13.2 Fuel-Oil Piping and Storage, Above Ground; On the Lowest Floor Inside a Building
limitations near subways. Regardless of capacity, fuel-oil tanks located within the outer lines of the subway, or within 20 feet (6096 mm) of the outside line ...
NYC Mechanical Code 2008 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.13 Installation of Tanks > 1305.13.2 Above Ground; On the Lowest Floor Inside a Building
1305.13.2 Fuel-Oil Piping and Storage, Above Ground; On the Lowest Floor Inside a Building
at or below 25 percent of the Lower Flammable Limit (LFL) of the fuel oil being used.
Containment. Fuel-oil tanks having a capacity of more than 660 ...
NYC Mechanical Code 2022 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.13 Installation of Tanks > 1305.13.2 Above Ground; On the Lowest Floor Inside a Building
1305.13.2 Fuel-Oil Piping and Storage, Above Ground; On the Lowest Floor Inside a Building
the portion of the tank up to the height of the containment. Special limitations near subways. Regardless of capacity, fuel-oil tanks located within ...
NYC Mechanical Code 2014 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.13 Installation of Tanks > 1305.13.2 Above Ground; On the Lowest Floor Inside a Building
1305.13 Fuel-Oil Piping and Storage, Installation of Tanks
foundation wall or footing.
Special limitations near subways. Regardless of capacity, no fuel-oil tank shall be placed within 20 feet (6096 mm ...
NYC Mechanical Code 2022 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.13 Installation of Tanks
1305.8.4 Fuel-Oil Piping and Storage, Capacity
the required emergency vent flow while limiting the backpressure to less than the maximum pressure permitted by the design of the tank. Additionally ...
NYC Mechanical Code 2014 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.8 Emergency Relief Vent Piping > 1305.8.4 Capacity