406.12 Tamper-Resistant Receptacles
JUMP TO FULL CODE CHAPTER
All 15- and 20-ampere, 125-and 250-volt nonlocking-type receptacles in the areas specified in 406.12(1) through (8) shall be listed tamper-resistant receptacles.
- Dwelling units, including attached and detached garages and accessory buildings to dwelling units, and common areas of multifamily dwellings specified in 210.52 and 550.13
- Guest rooms and guest suites of hotels, motels, and their common areas
- Child care facilities
- Preschools and education facilities
- Business offices, corridors, waiting rooms and the like in clinics, medical and dental offices, and outpatient facilities
- Subset of assembly occupancies described in 518.2 to include places of awaiting transportation, gymnasiums, skating rinks, and auditoriums
- Dormitory units
- Assisted living facilities
Informational Note No. 1: This requirement would include receptacles identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2016, Wiring Devices — Dimensional Specifications.
Informational Note No. 2: Assisted living facilities are Institutional Use Group I-1 per IBC 2015.
Exception to (1), (2), (3), (4), (5), (6), (7) and (8): Receptacles in the following locations shall not be required to be tamper resistant:
- Receptacles located more than 1.7 m (5 1/2 ft) above the floor
- Receptacles that are part of a luminaire or appliance
- A single receptacle, or a duplex receptacle for two appliances, located within the dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug-connected in accordance with 400.10(A)(6), (A)(7), or (A)(8)
- Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a)
Related Code Sections
406.12 Equipment for General Use, Tamper-Resistant Receptacles
All 15- and 20-ampere, 125-and 250-volt nonlocking-type receptacles in the areas specified in 406.12(1) through (8) shall be listed tamper-resistant ...
National Electrical Code 2020 of Illinois > 4 Equipment for General Use > 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) > 406.12 Tamper-Resistant Receptacles
406.12 Equipment for General Use, Tamper-Resistant Receptacles
All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in the areas specified in 406.12(1) through (7) shall be listed tamper-resistant ...
National Electrical Code 2017 of Illinois > 4 Equipment for General Use > 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) > 406.12 Tamper-Resistant Receptacles
406.4 Equipment for General Use, General Installation Requirements
Listed tamper-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required ...
National Electrical Code 2017 of Illinois > 4 Equipment for General Use > 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) > 406.4 General Installation Requirements
(A) Special Occupancies, 20-Ampere
, 125-volt weather-resistant receptacle. This receptacle, when used in recreational vehicle site electrical equipment, shall not be required ...
National Electrical Code 2020 of Illinois > 5 Special Occupancies > 551 Recreational Vehicles and Recreational Vehicle Parks > 551.71 Type Receptacles Provided > (A) 20-Ampere
Article 406 Equipment for General Use, Receptacles, Cord Connectors, and Attachment Plugs (Caps)
of receptacles. Listed tamper-resistant receptacles shall ...
National Electrical Code 2017 of Illinois > 4 Equipment for General Use > 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps)