UpCodes logo
Go To Full Code Chapter
This paragraph applies to stationary, nonrefrigerated storage installations utilizing containers other than those covered in paragraph (e) of this section. Paragraph (b) of this section applies to this paragraph unless otherwise noted.
1910.111(c)(1) Design Pressure and Construction of Containers
The minimum design pressure for nonrefrigerated containers shall be 250 p.s.i.g.
1910.111(c)(2) Container Valves and Accessories, Filling and Discharge Connections
1910.111(c)(2)(i)
Each filling connection shall be provided with combination back-pressure check valve and excess-flow valve; one double or two single back-pressure check valves; or a positive shutoff valve in conjunction with either an internal back-pressure check valve or an internal excess flow valve.
1910.111(c)(2)(iii)
Each storage container shall be provided with a pressure gage graduated from 0 to 400 p.s.i. Gages shall be designated for use in ammonia service.
1910.111(c)(2)(iv)
All containers shall be equipped with vapor return valves.
1910.111(c)(2)(ii)
All liquid and vapor connections to containers except filling pipes, safety relief connections, and liquid-level gaging and pressure gage connections provided with orifices not larger than No. 54 drill size as required in paragraphs (b)(6) (iv) and (v) of this section shall be equipped with excess-flow valves.
1910.111(c)(3) Safety-Relief Devices
1910.111(c)(3)(i)
Every container shall be provided with one or more safety-relief valves of the spring-loaded or equivalent type in accordance with paragraph (b)(9) of this section.
1910.111(c)(3)(iii)
On underground installations where there is a probability of the manhole or housing becoming flooded, the discharge from vent lines shall be located above the high water level. All manholes or housings shall be provided with ventilated louvers or their equivalent, the area of such openings equaling or exceeding combined discharge areas of safety-relief valves and vent lines which discharge their content into the manhole housing.
1910.111(c)(3)(iv)
Vent pipes, when used, shall not be restricted or of smaller diameter than the relief-valve outlet connection.
1910.111(c)(3)(v)
If desired, vent pipes from two or more safety-relief devices located on the same unit, or similar lines from two or more different units may be run into a common discharge header, provided the capacity of such header is at least equal to the sum of the capacities of the individual discharge lines.
1910.111(c)(3)(ii)
The rate of discharge of spring-loaded safety relief valves installed on underground containers may be reduced to a minimum of 30 percent of the rate of discharge specified in Table H-36. Containers so protected shall not be uncovered after installation until the liquid ammonia has been removed. Containers which may contain liquid ammonia before being installed underground and before being completely covered with earth are to be considered aboveground containers when determining the rate of discharge requirements of the safety-relief valves.
1910.111(c)(4) Reinstallation of Containers
1910.111(c)(4)(i)
Containers once installed under ground shall not later be reinstalled above ground or under ground, unless they successfully withstand hydrostatic pressure retests at the pressure specified for the original hydrostatic test as required by the code under which constructed and show no evidence of serious corrosion.
1910.111(c)(4)(ii)
Where containers are reinstalled above ground, safety devices or gaging devices shall comply with paragraph (b)(9) of this section and this paragraph respectively for aboveground containers.
1910.111(c)(5) Installation of Storage Containers
1910.111(c)(5)(i)
Containers installed above ground, except as provided in paragraph (c)(5)(v) of this section shall be provided with substantial concrete or masonry supports, or structural steel supports on firm concrete or masonry foundations. All foundations shall extend below the frost line.
1910.111(c)(5)(iii)
Containers installed under ground shall be so placed that the top of the container is below the frost line and in no case less than 2 feet below the surface of the ground. Should ground conditions make compliance with these requirements impracticable, installation shall be made otherwise to prevent physical damage. It will not be necessary to cover the portion of the container to which manhole and other connections are affixed. When necessary to prevent floating, containers shall be securely anchored or weighted.
1910.111(c)(5)(iv)
Underground containers shall be set on a firm foundation (firm earth may be used) and surrounded with earth or sand well tamped in place. The container, prior to being placed under ground, shall be given a corrosion resisting protective coating. The container thus coated shall be so lowered into place as to prevent abrasion or other damage to the coating.
1910.111(c)(5)(v)
Containers with foundations attached (portable or semiportable tank containers with suitable steel "runners" or "skids" and commonly known in the industry as "skid tanks") shall be designed and constructed in accordance with paragraph (c)(1) of this section.
1910.111(c)(5)(vi)
Secure anchorage or adequate pier height shall be provided against container flotation wherever sufficiently high flood water might occur.
1910.111(c)(5)(vii)
The distance between underground containers of over 2,000 gallons capacity shall be at least 5 feet.
1910.111(c)(5)(ii)
Horizontal aboveground containers shall be so mounted on foundations as to permit expansion and contraction. Every container shall be supported to prevent the concentration of excessive loads on the supporting portion of the shell. That portion of the container in contact with foundations or saddles shall be protected against corrosion.
1910.111(c)(6) Protection of Appurtenances
1910.111(c)(6)(i)
Valves, regulating, gaging, and other appurtenances shall be protected against tampering and physical damage. Such appurtenances shall also be protected during transit of containers.
1910.111(c)(6)(ii)
All connections to underground containers shall be located within a dome, housing, or manhole and with access thereto by means of a substantial cover.
1910.111(c)(7) Damage From Vehicles
Precaution shall be taken against damage to ammonia systems from vehicles.

Related Code Sections