This paragraph covers the general requirements for all circuits and equipment operated at over 600 volts.
1910.308(a)(1) Aboveground Wiring Methods
1910.308(a)(1)(i)
Aboveground conductors shall be installed in rigid metal conduit, in intermediate metal conduit, in electrical metallic tubing, in rigid nonmetallic conduit, in cable trays, as busways, as cablebus, in other identified raceways, or as open runs of metal-clad cable suitable for the use and purpose. In locations accessible to qualified persons only, open runs of Type MV cables, bare conductors, and bare busbars are also permitted. Busbars shall be either copper or aluminum. Open runs of insulated wires and cables having a bare lead sheath or a braided outer covering shall be supported in a manner designed to prevent physical damage to the braid or sheath.
1910.308(a)(1)(ii)
Conductors emerging from the ground shall be enclosed in approved raceways.
1910.308(a)(2) Braid-Covered Insulated Conductors -- Open Installations
The braid on open runs of braid-covered insulated conductors shall be flame retardant or shall have a flame-retardant saturant applied after installation. This treated braid covering shall be stripped back a safe distance at conductor terminals, according to the operating voltage.
1910.308(a)(3) Insulation Shielding
1910.308(a)(3)(i)
Metallic and semiconductor insulation shielding components of shielded cables shall be removed for a distance dependent on the circuit voltage and insulation. Stress reduction means shall be provided at all terminations of factory-applied shielding.
1910.308(a)(3)(ii)
Metallic shielding components such as tapes, wires, or braids, or combinations thereof, and their associated conducting and semiconducting components shall be grounded.
1910.308(a)(4) Moisture or Mechanical Protection for Metal-Sheathed Cables
Where cable conductors emerge from a metal sheath and where protection against moisture or physical damage is necessary, the insulation of the conductors shall be protected by a cable sheath terminating device.
1910.308(a)(5) Interrupting and Isolating Devices
1910.308(a)(5)(i)
Circuit breaker installations located indoors shall consist of metal-enclosed units or fire-resistant cell-mounted units. In locations accessible only to qualified employees, open mounting of circuit breakers is permitted. A means of indicating the open and closed position of circuit breakers shall be provided.
1910.308(a)(5)(iii)
Fused cutouts installed in buildings or transformer vaults shall be of a type identified for the purpose. Distribution cutouts may not be used indoors, underground, or in metal enclosures. They shall be readily accessible for fuse replacement.
1910.308(a)(5)(iv)
Where fused cutouts are not suitable to interrupt the circuit manually while carrying full load, an approved means shall be installed to interrupt the entire load. Unless the fused cutouts are interlocked with the switch to prevent opening of the cutouts under load, a conspicuous sign shall be placed at such cutouts reading: "WARNING -- DO NOT OPERATE UNDER LOAD."
1910.308(a)(5)(v)
Suitable barriers or enclosures shall be provided to prevent contact with nonshielded cables or energized parts of oil-filled cutouts.
1910.308(a)(5)(vi)
Load interrupter switches may be used only if suitable fuses or circuits are used in conjunction with these devices to interrupt fault currents.
1910.308(a)(5)(vi)(A)
Where these devices are used in combination, they shall be coordinated electrically so that they will safely withstand the effects of closing, carrying, or interrupting all possible currents up to the assigned maximum short-circuit rating.
1910.308(a)(5)(vi)(B)
Where more than one switch is installed with interconnected load terminals to provide for alternate connection to different supply conductors, each switch shall be provided with a conspicuous sign reading: "WARNING -- SWITCH MAY BE ENERGIZED BY BACKFEED."
1910.308(a)(5)(vii)
A means (for example, a fuseholder and fuse designed for the purpose) shall be provided to completely isolate equipment for inspection and repairs. Isolating means that are not designed to interrupt the load current of the circuit shall be either interlocked with an approved circuit interrupter or provided with a sign warning against opening them under load.
1910.308(a)(5)(ii)
Where fuses are used to protect conductors and equipment, a fuse shall be placed in each ungrounded conductor. Two power fuses may be used in parallel to protect the same load, if both fuses have identical ratings, and if both fuses are installed in an identified common mounting with electrical connections that will divide the current equally. Power fuses of the vented type may not be used indoors, underground, or in metal enclosures unless identified for the use.
1910.308(a)(6) Mobile and Portable Equipment
1910.308(a)(6)(i)
A metallic enclosure shall be provided on the mobile machine for enclosing the terminals of the power cable. The enclosure shall include provisions for a solid connection for the grounding terminal to effectively ground the machine frame. The method of cable termination used shall prevent any strain or pull on the cable from stressing the electrical connections. The enclosure shall have provision for locking so only authorized qualified persons may open it and shall be marked with a sign warning of the presence of energized parts.
1910.308(a)(6)(ii)
All energized switching and control parts shall be enclosed in effectively grounded metal cabinets or enclosures. Circuit breakers and protective equipment shall have the operating means projecting through the metal cabinet or enclosure so these units can be reset without locked doors being opened. Enclosures and metal cabinets shall be locked so that only authorized qualified persons have access and shall be marked with a sign warning of the presence of energized parts. Collector ring assemblies on revolving-type machines (shovels, draglines, etc.) shall be guarded.
1910.308(a)(7) Tunnel Installations
This paragraph applies to installation and use of high-voltage power distribution and utilization equipment that is portable or mobile, such as substations, trailers, cars, mobile shovels, draglines, hoists, drills, dredges, compressors, pumps, conveyors, and underground excavators.
1910.308(a)(7)(i)
Conductors in tunnels shall be installed in one or more of the following:
1910.308(a)(7)(i)(A) Metal Conduit or Other Metal Raceway
1910.308(a)(7)(i)(B) Type MC Cable; or
1910.308(a)(7)(i)(C) Other Approved Multiconductor Cable
1910.308(a)(7)(iii)
Conductors and cables shall also be so located or guarded as to protect them from physical damage. An equipment grounding conductor shall be run with circuit conductors inside the metal raceway or inside the multiconductor cable jacket. The equipment grounding conductor may be insulated or bare.
1910.308(a)(7)(iv)
Bare terminals of transformers, switches, motor controllers, and other equipment shall be enclosed to prevent accidental contact with energized parts.
1910.308(a)(7)(v)
Enclosures for use in tunnels shall be drip-proof, weatherproof, or submersible as required by the environmental conditions.
1910.308(a)(7)(vi)
Switch or contactor enclosures may not be used as junction boxes or raceways for conductors feeding through or tapping off to other switches, unless special designs are used to provide adequate space for this purpose.
1910.308(a)(7)(vii)
A disconnecting means that simultaneously opens all ungrounded conductors shall be installed at each transformer or motor location.
1910.308(a)(7)(viii)
All nonenergized metal parts of electric equipment and metal raceways and cable sheaths shall be effectively grounded and bonded to all metal pipes and rails at the portal and at intervals not exceeding 305 m (1000 ft) throughout the tunnel.
1910.308(a)(7)(ii)
Multiconductor portable cable may supply mobile equipment.

Related Code Sections

1910.308(a) Electrical, Systems Over 600 Volts, Nominal
This paragraph covers the general requirements for all circuits and equipment operated at over 600 volts ...
1910.308(a)(6) Electrical, Mobile and Portable Equipment
A metallic enclosure shall be provided on the mobile machine for enclosing the terminals of the power cable. The enclosure shall include provisions ...
1910.308(a)(7) Electrical, Tunnel Installations
This paragraph applies to installation and use of high-voltage power distribution and utilization equipment that is portable or mobile ...
1910.308(a)(3)(i) Electrical,
Metallic and semiconductor insulation shielding components of shielded cables shall be removed for a distance dependent on the circuit voltage ...