1324.5.2.3 System to Be Charged
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.2 Initial Cross-Connection Test > 1324.5.2.3 System to Be Charged
Go To Full Code Chapter
The system under test shall be charged with oil-free, dry nitrogen NF to a gauge pressure of 50 psi (345 kPa). [NFPA 99:5.1.12.2.4.3]
Related Code Sections
1324.5.2.3 Health Care Facilities and Medical Gas and Medical Vacuum Systems, System to Be Charged
The system under test shall be charged with oil-free, dry nitrogen NF to a gauge pressure of 50 psi (345 kPa). [NFPA 99:5.1.12.2.4.3] ...
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.2 Initial Cross-Connection Test > 1324.5.2.3 System to Be Charged
(A) Special Occupancies, Battery Charging Equipment
Battery chargers and their control equipment, and batteries being charged, shall not be located within locations classified in 511.3 ...
26.7.2.1 Marine Systems,
be provided for maintaining an air pressure in the tank such that, while the standing charge of water is being expended, the pressure will not be less than ...
706.33 Special Conditions, Charge Control
Systems using interactive inverters to control energy storage state-of-charge by diverting excess power ...
(E) Special Occupancies, Battery-Powered Appliances
Battery-powered appliances shall not be capable of being charged while in operation unless their charging circuitry incorporates an integral ...