905.2.1.2 System Testing and Pipe Size
JUMP TO FULL CODE CHAPTER
The standpipe system shall be able to provide the pressure and flow rate required by NFPA 14 when the standpipe system is supported by local fire department apparatus through the fire department connection as verified with hydraulic calculations. The hydraulic calculations are to be performed between the hydraulically most demanding standpipe hose connection and the fire department connection. Pipe sizes shall not be less than the minimum requirements in NFPA 14.
Related Code Sections
905.2.1.2 Fire Protection Systems, System Testing and Pipe Size
between the hydraulically most demanding standpipe hose connection and the fire department connection. Pipe sizes shall not be less than the minimum ...
Minnesota Fire Code 2015 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.2 Installation Standard > 905.2.1 Modification to Standards > 905.2.1.2 System Testing and Pipe Size
905.2.1.2 Fire Protection Systems, System Testing and Pipe Size
between the hydraulically most demanding standpipe hose connection and the fire department connection. Pipe sizes shall not be less than the minimum ...
Minnesota Building Code 2015 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.2 Installation Standard > 905.2.1 Modification to Standards > 905.2.1.2 System Testing and Pipe Size
7.2.3* System Requirements, Size of Systems
occupancy, system size shall be such that initial water is discharged from the system test connection in not more than 15 seconds, starting at the normal air ...
Standard for the Installation of Sprinkler Systems 2016 of Minnesota > 7 System Requirements > 7.2* Dry Pipe Systems > 7.2.3* Size of Systems
Section 1201 Hydronic Piping, General
Piping and piping system components for hydronic systems shall be sized for the demand of the system ...
Section 1201 Hydronic Piping, General
Piping and piping system components for hydronic systems shall be sized for the demand of the system ...