50.4.9 System Supervision
JUMP TO FULL CODE CHAPTER
System supervision shall not be required where a fire-extinguishing system(s) is interconnected or interlocked with the cooking equipment power source(s) so that if the fire-extinguishing system becomes inoperable due to power failure, all sources of fuel or electrical power that produce heat to all cooking equipment serviced by that hood shall automatically shut off. [96:10.7.3]
Related Code Sections
50.4.9 Commercial Cooking, System Supervision
] System supervision shall not be required where a fire-extinguishing system(s ...
Fire Code 2015 of Delaware > 50 Commercial Cooking > 50.4 Fire-Extinguishing Equipment > 50.4.9 System Supervision
26.3.3 Marine Systems, System Piping Supervision
All preaction sprinkler systems shall be supervised regardless of the number of sprinklers supplied ...
Standard for the Installation of Sprinkler Systems 2013 of Delaware > 26 Marine Systems > 26.3 System Requirements > 26.3.3 System Piping Supervision
30.3.3 Marine Systems, System Piping Supervision
All preaction sprinkler systems shall be supervised regardless of the number of sprinklers supplied ...
Standard for the Installation of Sprinkler Systems 2019 of Delaware > 30 Marine Systems > 30.3 System Requirements > 30.3.3 System Piping Supervision
7.3.2.4.1 System Requirements,
Sprinkler piping and fire detection devices shall be automatically supervised where more than 20 sprinklers are on the system ...
Standard for the Installation of Sprinkler Systems 2013 of Delaware > 7 System Requirements > 7.3 Preaction Systems and Deluge Systems > 7.3.2 Preaction Systems > 7.3.2.4* Supervision > 7.3.2.4.1
7.3.2.4.4 System Requirements,
All preaction system types described in 7.3.2.1(2) and 7.3.2.1(3) shall maintain a minimum supervising air or nitrogen pressure of 7 psi (0.5 bar) ...
Standard for the Installation of Sprinkler Systems 2013 of Delaware > 7 System Requirements > 7.3 Preaction Systems and Deluge Systems > 7.3.2 Preaction Systems > 7.3.2.4* Supervision > 7.3.2.4.4