Section 1102 System Requirements

Mechanical Code 2015 of Utah > 11 Refrigeration > 1102 System Requirements
JUMP TO FULL CODE CHAPTER

1102.1 General

The system classification, allowable refrigerants, maximum quantity, enclosure requirements, location limitations, and field pressure test requirements shall be determined as follows:

1. Determine the refrigeration system's classification, in accordance with Section 1103.3.

2. Determine the refrigerant classification in accordance with Section 1103.1.

3. Determine the maximum allowable quantity of refrigerant in accordance with Section 1104, based on type of refrigerant, system classification and occupancy.

4. Determine the system enclosure requirements in accordance with Section 1104.

5. Refrigeration equipment and appliance location and installation shall be subject to the limitations of Chapter 3.

6. Nonfactory-tested, field-erected equipment and appliances shall be pressure tested in accordance with Section 1108.

1102.2 Refrigerants

The refrigerant shall be that which the equipment or appliance was designed to utilize or converted to utilize. Refrigerants not identified in Table 1103.1 shall be approved before use.

1102.2.1 Mixing

Refrigerants, including refrigerant blends, with different designations in ASHRAE 34 shall not be mixed in a system.

Exception: Addition of a second refrigerant is allowed where permitted by the equipment or appliance manufacturer to improve oil return at low temperatures. The refrigerant and amount added shall be in accordance with the manufacturer’s instructions.

1102.2.2 Purity

Refrigerants used in refrigeration systems shall be new, recovered or reclaimed refrigerants in accordance with Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3. Where required by the equipment or appliance owner or the code official, the installer shall furnish a signed declaration that the refrigerant used meets the requirements of Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3.

Exception: The refrigerant used shall meet the purity specifications set by the manufacturer of the equipment or appliance in which such refrigerant is used where such specifications are different from that specified in Sections 1102.2.2.1, 1102.2.2.2 and 1102.2.2.3.

1102.2.2.1 New Refrigerants

Refrigerants shall be of a purity level specified by the equipment or appliance manufacturer.

1102.2.2.2 Recovered Refrigerants

Refrigerants that are recovered from refrigeration and air-conditioning systems shall not be reused in other than the system from which they were recovered and in other systems of the same owner. Recovered refrigerants shall be filtered and dried before reuse. Recovered refrigerants that show clear signs of contamination shall not be reused unless reclaimed in accordance with Section 1102.2.2.3.

1102.2.2.3 Reclaimed Refrigerants

Used refrigerants shall not be reused in a different owner’s equipment or appliances unless tested and found to meet the purity requirements of ARI 700. Contaminated refrigerants shall not be used unless reclaimed and found to meet the purity requirements of ARI 700.

1102.3 Access Port Protection

Refrigerant access ports shall be protected in accordance with Section 1101.10 whenever refrigerant is added to or recovered from refrigeration or air-conditioning systems.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1009.8.1 Means of Egress, System Requirements
Two-way communication systems shall provide communication between each required location and the fire command center or a central control point ...
Building Code 2015 of Utah > 10 Means of Egress > 1009 Accessible Means of Egress > 1009.8 Two-Way Communication > 1009.8.1 System Requirements
1009.8.1 Means of Egress, System requirements
Two-way communication systems shall provide communication between each required location and the fire command center or a central control point ...
Building Code 2018 of Utah > 10 Means of Egress > 1009 Accessible Means of Egress > 1009.8 Two-way communication > 1009.8.1 System requirements
Section 1102 Refrigeration, System Requirements
The system classification, allowable refrigerants, maximum quantity, enclosure requirements, location limitations, and field pressure test ...
Mechanical Code 2018 of Utah > 11 Refrigeration > 1102 System Requirements
Section 1102 Refrigeration, System Requirements
The system classification, allowable refrigerants, maximum quantity, enclosure requirements, location limitations, and field pressure test ...
Mechanical Code 2015 of Utah > 11 Refrigeration > 1102 System Requirements
502.8.1.1 Exhaust Systems, System Requirements
Exhaust ventilation systems shall comply with all of the following: 1. The installation shall be in accordance with this code. 2. Mechanical ...
Mechanical Code 2015 of Utah > 5 Exhaust Systems > 502 Required Systems > 502.8 Hazardous Materials‒general Requirements > 502.8.1 Storage in Excess of the Maximum Allowable Quantities > 502.8.1.1 System Requirements
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US