Metal hydride hydrogen storage systems shall be marked with the following:
  1. Manufacturer's name;
  2. Manufacturer's emergency contact information;
  3. A unique code or serial number specific to the system;
  4. System name or product code that identifies the system by the type of chemistry used in the system;
  5. Limitations on refilling of containers that include rated charging pressure and capacity; and
  6. Service life indicating the last date the metal hydride hydrogen storage system can be used.