(i) 907.2.1.1 System Initiation of Group A Occupancies With an Occupant Load of 1,000 or More
JUMP TO FULL CODE CHAPTER
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm communications system in accordance with paragraph (G)(5)(b)(ii)(907.5.2.2) of this rule.
Exception: Where approved, the prerecorded announcement is allowed to be manually deactivated for a period of time, not to exceed 3 minutes, for the sole purpose of allowing a live voice announcement from an approved, constantly attended location.
Related Code Sections
907.2.1.1 Fire Protection Systems, System Initiation in Group A Occupancies With an Occupant Load of 1,000 or More
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm ...
Ohio Building Code 2017 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.1 Group A > 907.2.1.1 System Initiation in Group A Occupancies With an Occupant Load of 1,000 or More
907.2.1.1 Fire Protection Systems, System Initiation in Group A Occupancies With an Occupant Load of 1,000 or More
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm ...
Ohio Building Code 2011 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.1 Group A > 907.2.1.1 System Initiation in Group A Occupancies With an Occupant Load of 1,000 or More
907.2.1.1 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, System Initiation of Group A Occupancies With an Occupant Load of 1,000 or More
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required-New Buildings and Structures > 907.2.1 Group A > 907.2.1.1 System Initiation of Group A Occupancies With an Occupant Load of 1,000 or More
907.2.1.1 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, System Initiation of Group A Occupancies With an Occupant Load of 1,000 or More
Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm ...
2017 Ohio Fire Code > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required-New Buildings and Structures > 907.2.1 Group A > 907.2.1.1 System Initiation of Group A Occupancies With an Occupant Load of 1,000 or More
903.2.1 Fire Protection Systems, Group A
An automatic sprinkler system shall be provided throughout buildings and portions thereof used as Group A occupancies as provided in this section ...
Ohio Building Code 2017 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.1 Group A