// CODE SNIPPET
(A) System Grounding Connections
Go To Full Code Chapter
A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor, at each service, in accordance with 250.24(A)(1) through (A)(5).
(1) General
The grounding electrode conductor connection shall be made at any accessible point from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral to, including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means.
Informational Note: See definitions of Service Conductors, Overhead; Service Conductors, Underground; Service Drop; and Service Lateral in Article 100.
(2) Outdoor Transformer
Where the transformer supplying the service is located outside the building, at least one additional grounding connection shall be made from the grounded service conductor to a grounding electrode, either at the transformer or elsewhere outside the building.
Exception: The additional grounding electrode conductor connection shall not be made on high-impedance grounded neutral systems. The system shall meet the requirements of 250.36.
(3) Dual-Fed Services
For services that are dual fed (double ended) in a common enclosure or grouped together in separate enclosures and employing a secondary tie, a single grounding electrode conductor connection to the tie point of the grounded conductor(s) from each power source shall be permitted.
(4) Main Bonding Jumper as Wire or Busbar
Where the main bonding jumper specified in 250.28 is a wire or busbar and is installed from the grounded conductor terminal bar or bus to the equipment grounding terminal bar or bus in the service equipment, the grounding electrode conductor shall be permitted to be connected to the equipment grounding terminal, bar, or bus to which the main bonding jumper is connected.
(5) Load-Side Grounding Connections
A grounded conductor shall not be connected to normally non—current-carrying metal parts of equipment, to equipment grounding conductor(s), or be reconnected to ground on the load side of the service disconnecting means except as otherwise permitted in this article.
Related Code Sections
(A) Wiring and Protection, System Grounding Connections
A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor ...
(A) Wiring and Protection, System Grounding Connections
A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor ...
690.42 Special Equipment, Point of System Grounding Connection
Systems with a ground-fault protective device in accordance with 690.41(B) shall have any current-carrying conductor-to-ground connection made ...
690.42 Special Equipment, Point of System Grounding Connection
Systems with a ground-fault protective device in accordance with 690.41(B) shall have any current-carrying conductor-to-ground connection made ...
(5) Wiring and Protection, Load-Side Grounding Connections
for separately derived systems, 250.32 for connections at separate buildings or structures, and 250.142 for use of the grounded circuit conductor ...