(B) System Capacity
JUMP TO FULL CODE CHAPTER
Where automatic transfer equipment is used, an optional standby system shall comply with 702.4(B)(2)(a) or (B)(2)(b) in accordance with Article 220 or by another approved method.
(a) Full Load. The standby source shall be capable of supplying the full load that is transferred by the automatic transfer equipment.
(b) Load Management. Where a system is employed that will automatically manage the connected load, the standby source shall have a capacity sufficient to supply the maximum load that will be connected by the load management system.
Related Code Sections
(B) Special Conditions, System Capacity
Where manual transfer equipment is used, an optional standby system shall have adequate capacity and rating for the supply of all equipment intended ...
National Electrical Code 2020 of Texas > 7 Special Conditions > 702 Optional Standby Systems > 702.4 Capacity and Rating > (B) System Capacity
920.2 Vents, System Capacity
The vent system shall be based on the air capacity requirements of the drainage system under a peak load condition ...
Plumbing Code of the Texas Industrialized Housing and Buildings Program > 9 Vents > 920 Computerized Vent Design > 920.2 System Capacity
7.2.13.2 Means of Egress, Elevator Evacuation System Capacity
The elevator car shall have a capacity of not less than eight persons ...
Life Safety Code 2015 of Texas > 7 Means of Egress > 7.2 Means of Egress Components > 7.2.13 Elevators in Towers > 7.2.13.2 Elevator Evacuation System Capacity
(B) Special Conditions, Capacity
An emergency system shall have adequate capacity in accordance with Article 220 or by another approved method ...
National Electrical Code 2020 of Texas > 7 Special Conditions > 700 Emergency Systems > 700.4 Capacity and Rating > (B) Capacity
(B) Special Conditions, Capacity
A legally required standby system shall have adequate capacity in accordance with Article 220 or by another approved method ...
National Electrical Code 2020 of Texas > 7 Special Conditions > 701 Legally Required Standby Systems > 701.4 Capacity and Rating > (B) Capacity