6.7.3.3.1 General
Construction documents shall require that all HVAC systems be balanced in accordance with generally accepted engineering standards (see Informative Appendix E). Construction documents shall require that a written balance report be provided to the building owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 ft2.
6.7.3.3.2 Air System Balancing
Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan system power greater than 1 hp, fan speed shall be adjusted to meet design flow conditions.
6.7.3.3.3 Hydronic System Balancing
Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.
Exceptions to 6.7.3.3.3
Impellers need not be trimmed nor pump speed adjusted
  1. for pumps with pump motors of 10 hp or less or
  2. when throttling results in no greater than 5% of the nameplate horsepower draw, or 3 hp, whichever is greater, above that required if the impeller was trimmed.

Related Code Sections

6.7.3.3 Heating, Ventilating, and Air Conditioning, System Balancing
Construction documents shall require that all HVAC systems be balanced in accordance with generally accepted engineering standards (see Informative ...
L 501.6 Sustainable Practices, System Balancing
Systems with multiple recirculation zones shall be balanced to distribute hot water uniformly, or they shall be operated with a pump for each zone ...
403.3.1.5 Ventilation, Balancing
rate as required by Sections 403.3 and 403.3.1.2. Ventilation systems shall be balanced by an approved method. Such balancing shall verify ...
510.6.1 Exhaust Systems, Balancing
Systems conveying explosive or radioactive materials shall be prebalanced by duct sizing. Other systems shall be balanced by duct sizing ...