907.2.6.3.4 System Annunciation
JUMP TO FULL CODE CHAPTER
A staff alerting fire alarm shall sound at all staff control stations on the floor of activation and an audible and visual signal shall be indicated on an annunciator at the facility control center upon activation of any automatic extinguishing system, automatic detection system, or any smoke detector or manual actuating or initiating device. In addition, where there are staff-control stations on the floor, an audible, visual and manual alarm shall be located in each staff control station.
Fire and trouble signals of fire alarm systems and sprinkler water-flow and supervisory signals of extinguishing systems shall be annunciated in an area designated as the facility control center which shall be constantly attended by staff personnel. All such signals shall produce both an audible signal and visual display at the facility control center indicating the building, floor zone or other designated area from which the signal originated in accordance with Section 907.6.4.
All local detention facilities within the scope of Section 6031.4 of the Penal Code shall have a automatic smoke detection system. A manual fire alarm-initiating device shall be installed in all guard control stations and shall be capable of alerting personnel in a central control point to the presence of fire or smoke within the facility.
Related Code Sections
513.6 Exhaust Systems, System Annunciation
Upon activation of an automatic
fire-extinguishing system, an audible alarm or visual
indicator shall be provided to show that the system has ...
California Mechanical Code 2019 > 5 Exhaust Systems > 513.0 Fire-Extinguishing Equipment > 513.6 System Annunciation
513.6 Exhaust Systems, System Annunciation
Upon activation of an automatic
fire-extinguishing system, an audible alarm or visual
indicator shall be provided to show that the system has ...
California Mechanical Code 2016 > 5 Exhaust Systems > 513.0 Fire-Extinguishing Equipment > 513.6 System Annunciation
907.2.6.3.4 Fire Protection Systems, System Annunciation
on an annunciator at the facility control center upon activation of any automatic extinguishing system, automatic detection system, or any smoke ...
California Building Code 2016 (Vol 1 & 2) > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.6 Group I > 907.2.6.3 Group I-3 Occupancies > 907.2.6.3.4 System Annunciation
907.2.6.3.4 Fire Protection Systems, System Annunciation
on an annunciator at the facility control center upon activation of any automatic extinguishing system, automatic detection system, or any smoke ...
California Fire Code 2016 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.6 Group I > 907.2.6.3 Group I-3 Occupancies > 907.2.6.3.4 System Annunciation
907.2.6.3.4 Fire Protection and Life Safety Systems, System Annunciation
on an annunciator at the facility control center upon activation of any automatic extinguishing system, automatic detection system, or any smoke ...
California Fire Code 2019 > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.6 Group I > 907.2.6.3 Group I-3 Occupancies > 907.2.6.3.4 System Annunciation