// CODE SNIPPET
404.2 Switch Connections
Go To Full Code Chapter
(A) Three-Way and Four-Way Switches
Three-way and four-way switches shall be wired so that all switching is done only in the ungrounded circuit conductor. Where in metal raceways or metal-armored cables, wiring between switches and outlets shall be in accordance with 300.20(A).
Exception: Switch loops shall not require a grounded conductor.
(B) Grounded Conductors
Switches or circuit breakers shall not disconnect the grounded conductor of a circuit.
Exception: A switch or circuit breaker shall be permitted to disconnect a grounded circuit conductor where all circuit conductors are disconnected simultaneously, or where the device is arranged so that the grounded conductor cannot be disconnected until all the ungrounded conductors of the circuit have been disconnected.
(C) Switches Controlling Lighting Loads
The grounded circuit conductor for the controlled lighting circuit shall be installed at the location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit serving bathrooms, hallways, stairways, and habitable rooms or occupiable spaces as defined in the applicable building code. Where multiple switch locations control the same lighting load such that the entire floor area of the room or space is visible from the single or combined switch locations, the grounded circuit conductor shall only be required at one location. A grounded conductor shall not be required to be installed at lighting switch locations under any of the following conditions:
- Where conductors enter the box enclosing the switch through a raceway, provided that the raceway is large enough for all contained conductors, including a grounded conductor
- Where the box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials
- Where snap switches with integral enclosures comply with 300.15(E)
- Where lighting in the area is controlled by automatic means
- Where a switch controls a receptacle load
The grounded conductor shall be extended to any switch location as necessary and shall be connected to switching devices that require line-to-neutral voltage to operate the electronics of the switch in the standby mode and shall meet the requirements of 404.22.
Exception: The connection requirement shall become effective on January 1, 2020. It shall not apply to replacement or retrofit switches installed in locations prior to local adoption of 404.2(C) and where the grounded conductor cannot be extended without removing finish materials. The number of electronic control switches on a branch circuit shall not exceed five, and the number connected to any feeder on the load side of a system or main bonding jumper shall not exceed 25. For the purpose of this exception, a neutral busbar, in compliance with 200.2(B) and to which a main or system bonding jumper is connected shall not be limited as to the number of electronic lighting control switches connected.
Informational Note: The provision for a (future) grounded conductor is to complete a circuit path for electronic lighting control devices.
Related Code Sections
404.2 Equipment for General Use, Switch Connections
controls a receptacle load The grounded conductor shall be extended to any switch location as necessary and shall be connected to switching ...
404.2 Equipment for General Use, Switch Connections
a receptacle load The grounded conductor shall be extended to any switch location as necessary and shall be connected to switching devices ...
(C) Equipment for General Use, Switches Controlling Lighting Loads
The grounded conductor shall be extended to any switch location as necessary and shall be connected to switching devices that require line-to-neutral ...
(C) Equipment for General Use, Connection of Switches
Single-throw knife switches and switches with butt contacts shall be connected such that their blades are de-energized when the switch is in the open ...
(C) Equipment for General Use, Connection of Switches
Single-throw knife switches and switches with butt contacts shall be connected such that their blades are de-energized when the switch is in the open ...