Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1.
Table 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates
Type of UseMinimum Maneuvering Clearance
Approach DirectionDoor or Gate SidePerpendicular to DoorwayParallel to Doorway (beyond latch side unless noted)
1. Add 12 inches (305 mm) if closer and latch are provide
2. Add 6 inches (150 mm) if closer and latch are provided.
3. Beyond hinge side.
4. Add 6 inches (150 mm) if closer is provided.
From front Pull 60 inches (1525 mm) 18 inches (455 mm)
From front Push 48 inches (1220 mm) 0 inches (0 mm) 1
From hinge side Pull 60 inches (1525 mm) 36 inches (915 mm)
From hinge side Pull 54 inches (1370 mm) 42 inches (1065 mm)
From hinge side Push 42 inches (1065 mm) 2 22 inches (560 mm) 3
From latch side Pull 48 inches (1220 mm) 4 24 inches (610 mm)
From latch side Push 42 inches (1065 mm) 4 24 inches (610 mm)
Figure 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates
Figures (a) — (c) Front Approaches.  Maneuvering space on the pull side extends 18 inches (455 mm) minimum beyond the latch side of the door and 60 inches (1525 mm) minimum perpendicular to the doorway.  On the push side of doors not equipped with a closer or latch, the maneuvering space is the same width as the door opening and extends 48 inches (1220 mm) minimum perpendicular to the doorway.  At doors equipped with both a closer and a latch, the maneuvering space extends 12 inches (305 mm) minimum beyond the latch side of the door and 48 inches (1220 mm) minimum perpendicular to the doorway.  Figures (d) — (f) Hinge Approaches.  Maneuvering space on the pull side extends 36 inches (915 mm) minimum beyond the latch side of the door and 60 inches (1525 mm) minimum perpendicular to the doorway; if this space extends 42 inches (1065 mm) minimum beyond the latch side of the door, it can extend 54 inches (1370 mm) minimum perpendicular to the doorway.
Figure (g) Hinge Approach.  On the push side, maneuvering space extends 22 inches (560 mm) from the hinge side of the doorway and 48 inches (1220 mm) minimum perpendicular to the doorway at doors with both a closer and a latch or 42 inches (1065 mm) at doors that do not have both a closer and a latch.  Figures (h) — (k) Latch Approaches.  Maneuvering space on the pull side extends 24 inches (915 mm) minimum beyond the latch side of the door and 54 inches (1525 mm) minimum perpendicular to the doorway; if the door has both a closer and a latch; if the door does not, the space can be 48 inches (1220 mm) minimum measured perpendicular to the doorway.  On the push side, maneuvering space extends 24 inches (560 mm) from the latch side of the doorway and 48 inches (1220 mm) minimum perpendicular to the doorway if the door has both a closer and a latch; if it does not, the space can extend 42 inches (1065 mm) minimum measured perpendicular to the doorway.

Related Code Sections

404.2.4.1 Accessible Routes, Swinging Doors and Gates
Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1. Table 404.2.4.1 Maneuvering Clearances at Manual ...
404 Accessible Routes, Doors, Doorways, and Gates
Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1. Table 404.2.4.1 ...
409.3 Accessible Routes, Elevator Doors
Hoistway doors, car doors, and car gates shall comply with 409.3 and 404. EXCEPTION: Doors shall not be required to comply with the maneuvering ...