Swimouts, located in either the deep or shallow area of a pool, shall comply with all of the following:
  1. The horizontal surface shall be not greater than 20 inches (508 mm) below the waterline.
  2. An unobstructed surface shall be provided that is equal to or greater than that required for the top tread of the pool stairs in accordance with Section 411.2.
  3. Where used as an entry and exit access, swimouts shall be provided with steps that comply with the pool stair requirements of Section 411.2.
  4. The leading edge shall be visibly set apart.

Related Code Sections

411.5.1 Public Swimming Pools, Swimouts
Swimouts, located in either the deep or shallow area of a pool, shall comply with all of the following: The horizontal surface shall be not greater ...
411.5.1 Public Swimming Pools, Swimouts
Swimouts, located in either the deep or shallow area of a pool, shall comply with all of the following: The horizontal surface shall be not greater ...
610.6 Aquatic Recreation Facilities, Swimouts
Swimouts shall be located completely outside of the water current or wave action of the pool or spa and can be located in shallow or deep areas ...
610.6 Aquatic Recreation Facilities, Swimouts
Swimouts shall be located completely outside of the water current or wave action of the pool or spa and can be located in shallow or deep areas ...
610.6.2 Aquatic Recreation Facilities, Step Required
Where a swimout is used as an entry and exit access point, it shall be provided with a step that meets the pool stair requirements (see Section 610.5) ...