1224.15.2.1 General Operating Room(s)
Each room shall have a minimum clear floor area of 400 square feet (37.16 m2) with a minimum of 20 feet (6096 mm) clear dimension between fixed cabinets and built-in shelves; and a system for emergency communication with the surgical service space control station. X-ray or imaging viewing capabilities shall be provided.
Exception: Where renovation of existing operating rooms is undertaken in facilities built under the 2001 or prior California Building Code, each operating room shall have a minimum clear floor area of 324 square feet (30.10 m2) with a minimum of 18 feet (5486 mm) clear dimension between fixed cabinets and built-in shelves.
1224.15.2.2 Procedure Room(s)
Where a procedure room is provided, it shall comply with Section 1224.4.4.1.4 unless specified elsewhere.
1224.15.2.2.1 Surgical Cystoscopic and Other Endourologic Procedures
Each room shall have a minimum clear floor area of 250 square feet (23.23 m2) with a minimum of 15 feet (4572 mm) clear dimension between fixed cabinets and built-in shelves. X-ray viewing and/or other imaging modality capabilities shall be provided
Exception: Where renovation of operating rooms is undertaken in facilities built under the 2001 or prior California Building Code rooms for surgical cystoscopy shall have a minimum clear floor area of 180 square feet (16.72 m2). Cast rooms for open reductions, if provided, shall have a minimum clear floor area of 180 square feet (16.72 m2), no dimension of which shall be less than 11 feet (3353 mm).

Related Code Sections

1224.15.2 Interior Environment, Surgery
Each room shall have a minimum clear floor area of 400 square feet (37.16 m2) with a minimum of 20 feet (6096 mm) clear dimension between fixed ...
1224.15.2 Interior Environment, Surgery
Each room shall have a minimum clear floor area of 400 square feet (37.16 m2) with a minimum of 20 feet (6096 mm) clear dimension between fixed ...
1224.15.2 Interior Environment, Surgery
Each room shall have a minimum clear floor area of 400 square feet (37.16 m2) with a minimum of 20 feet (6096 mm) clear dimension between fixed ...
1226.6.1.4 Interior Environment, Oral Surgery
When provided, treatment areas for procedures for which general anesthesia is used, shall comply with the requirements in Section 1226.8 ...