Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

R602.7.5 Supports for Headers

Residential Code 2018 of Kansas > 6 Wall Construction > R602 Wood Wall Framing > R602.7 Headers > R602.7.5 Supports for Headers
JUMP TO FULL CODE CHAPTER
Headers shall be supported on each end with one or more jack studs or with approved framing anchors in accordance with Table R602.7(1) or R602.7(2). The full-height stud adjacent to each end of the header shall be end nailed to each end of the header with four-16d nails (3.5 inches × 0.135 inches). The minimum number of full-height studs at each end of a header shall be in accordance with Table R602.7.5.
TABLE R602.7.5
MINIMUM NUMBER OF FULL-HEIGHT STUDS AT EACH END OF HEADERS IN EXTERIOR WALLSa
MAXIMUM

HEADER SPAN
(feet)
ULTIMATE DESIGN WIND SPEED
AND EXPOSURE CATEGORY
< 140 mph, Exposure B
or
< 130 mph, Exposure C
≤ 115 mph, Exposure Bb
411
621
821
1032
1232
1432
1642
1842
For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
  1. For header spans between those given, use the minimum number of fullheight studs associated with the larger header span.
  2. The tabulated minimum number of full-height studs is applicable where jack studs are provided to support the header at each end in accordance with Table R602.7(1). Where a framing anchor is used to support the header in lieu of a jack stud in accordance with Note d of Table R602.7(1), the minimum number of full-height studs at each end of a header shall be in accordance with requirements for wind speed < 140 mph, Exposure B.

Related Code Sections


R602.7.5 Wall Construction, Supports for Headers
Headers shall be supported on each end with one or more jack studs or with approved framing anchors in accordance with Table R602.7(1) or R602.7(2 ...
Residential Code 2018 of Kansas > 6 Wall Construction > R602 Wood Wall Framing > R602.7 Headers > R602.7.5 Supports for Headers
R804.3.4 Roof-Ceiling Construction, Headers
Roof-ceiling framing above wall openings shall be supported on headers. The allowable spans for headers in load-bearing walls shall not exceed ...
Residential Code 2018 of Kansas > 8 Roof-Ceiling Construction > R804 Cold-Formed Steel Roof Framing > R804.3 Roof Construction > R804.3.4 Headers
R802.9 Roof-Ceiling Construction, Framing of Openings
(1219 mm), the trimmer joists and the header joist shall be doubled and of sufficient cross section to support the ceiling joists or rafter framing ...
Residential Code 2018 of Kansas > 8 Roof-Ceiling Construction > R802 Wood Roof Framing > R802.9 Framing of Openings
2308.5.5.2 Wood, Openings in Interior Bearing Partitions
) are permitted to be used. Wall studs shall support the ends of the header in accordance with Table 2308.4.1.1(1) or 2308.4.1.1(2), as applicable ...
Building Code 2018 of Kansas > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.5 Wall Construction > 2308.5.5 Openings in Walls and Partitions > 2308.5.5.2 Openings in Interior Bearing Partitions
R610.8 Wall Construction, Headers
is in the direction of horizontal framing members supported by the header. The table provides for roof slopes between 3:12 and 12:12. The maximum roof overhang is 24 ...
Residential Code 2018 of Kansas > 6 Wall Construction > R610 Structural Insulated Panel Wall Construction > R610.8 Headers
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING