3314.9.4 Supported Scaffolds at the Edge
JUMP TO FULL CODE CHAPTER
Supported scaffolds located on a floor, working deck,
or roof and located within a distance from the edge of the roof or an unenclosed perimeter that is
equal to or less than one and one-half times the height of the scaffold shall:
- Be positively anchored or tied-back, and with all wheels or rollers secured by rope, cable, or chocking at the wheels in order to prevent movement; and
- Have all sides of the scaffold facing an unenclosed perimeter or the edge of a roof within a distance that is equal to or less than one and one-half times the height of the scaffold provided with guardrails and debris netting in accordance with Section 3314.8; or
- Have all material and equipment susceptible to dislodgement, and not being actively held by a person, secured in a manner to prevent dislodgement by wind or accidental impact.
Exception:
The above requirements shall not apply where vertical safety netting that meets
the requirements of Section 3308.5, or an approved alternate system, extends to cover the full
height and width of all unenclosed perimeters within a distance from the scaffold equal to or
less than one and one-half times the height of the scaffold.
Related Code Sections
3314.9.4 Safeguards During Construction or Demolition, Supported Scaffolds at the Edge
Supported scaffolds located on a floor, working deck, or roof and located within a distance from the edge of the roof or an unenclosed perimeter ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.9 Supported Scaffold > 3314.9.4 Supported Scaffolds at the Edge
3314.9.4 Safeguards During Construction or Demolition, Supported Scaffolds at the Edge
Supported scaffolds located on a floor, working deck,
or roof and located within a distance from the edge of the roof or an unenclosed perimeter ...
NYC Building Code 2022 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.9 Supported Scaffold > 3314.9.4 Supported Scaffolds at the Edge
3314.8.5 Safeguards During Construction or Demolition, Screen or Mesh Height
When screens or mesh are used, they shall extend from the top edge of the guardrail system to the scaffold platform and along the entire opening ...
NYC Building Code 2008 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.8 Guardrail System and Toeboards > 3314.8.5 Screen or Mesh Height
Section 3314 Safeguards During Construction or Demolition, Scaffolds
or structure by a davit.
A permit is not required for a supported scaffold, provided:
The scaffold is not an outrigger scaffold (thrust out);
No ...
3314.8 Safeguards During Construction or Demolition, Guardrail System and Toeboards
of the scaffold. The top edge height of the toprails ...
NYC Building Code 2008 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.8 Guardrail System and Toeboards