Supported scaffolds and outrigger scaffolds (thrust out) shall be designed by a registered design professional. Where the scaffold is to be located upon a sidewalk shed, the requirements of Section 3307.6.4.2.2 shall also apply.
Exception: Design is not required for a supported scaffold, provided Items 1 through 6 are complied with:
  1. The scaffold is not an outrigger scaffold (thrust out);
  2. No hoisting equipment with a manufacturer's rated capacity greater than 2,000 pounds (907kg) will be located on the scaffold;
  3. The scaffold will not be loaded, or designed to be loaded, in excess of 75 pounds per square foot (366.15 kg/m2 ) (e.g. a light duty scaffold, a medium duty scaffold, or a heavy duty scaffold);
  4. The scaffold is less than 40 feet (12 192mm) in height;
  5. Side-arm or end-arm scaffold brackets are used exclusively for the support of workers; and
  6. Where the scaffold has a height-to-base ratio (including outriggers supports, if used) of more than four to one (4:1), it is restrained in accordance with Section 3314.9.1.