Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas

Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas
JUMP TO FULL CODE CHAPTER

2.9-3.8.1 Reserved

2.9-3.8.2 Nurse or Control Station

2.9-3.8.2.1

A nurse or control station that meets the requirements in Section 2.1-3.8.2 (Nurse Station) shall be provided.

2.9-3.8.2.2

The nurse or control station shall be located to permit visual observation of all traffic entering the patient care and diagnostic areas.

2.9-3.8.3 — 2.9-3.8.7 Reserved

2.9-3.8.8 Medication Safety Zone

See Section 2.1-3.8.8 (Medication Safety Zones) for requirements.

2.9-3.8.9 — 2.9-3.8.11 Reserved

2.9-3.8.12 Soiled Workroom or Soiled Holding Room

2.9-3.8.12.1

A soiled workroom or soiled holding room that meets the requirements in Section 2.1-3.8.12 (Soiled Workroom or Soiled Holding Room) shall be provided.

2.9-3.8.12.2

The soiled workroom or soiled holding room shall be physically separated from all other areas of the facility.

2.9-3.8.12.3

The soiled workroom or soiled holding room shall be permitted to be shared with other clinical services in the same outpatient facility.

2.9-3.8.13 Equipment and Supply Storage

2.9-3.8.13.1 Reserved

2.9-3.8.13.2 General Equipment and Supply Storage

  1. Storage room(s) shall be provided for storage of equipment and clean clinical supplies (including anesthesia equipment and supplies) used in the procedure suite.
  2. At minimum, storage room(s) for equipment and clean clinical supplies shall have a combined floor area of 25 square feet (7.62 square meters) per procedure room.

2.9-3.8.13.3 Wheelchair Storage

See Section 2.1-3.8.13.3 (Wheelchair storage and parking space) for requirements.

2.9-3.8.13.4 Emergency Equipment Storage

Space for emergency resuscitation equipment and supplies shall be provided adjacent to the procedure room(s) and pre- and post-procedure patient care areas in accordance with Section 2.1-3.8.13.4 (Emergency equipment storage).

2.9-3.8.13.5 Medical Gas Storage

Storage in accordance with NFPA 99: Health Care Facilities Code, including space for reserve cylinders, shall be provided for medical gas(es) used in the facility.

2.9-3.8.14 Environmental Services Room

An environmental services room that meets the requirements in Section 2.1-5.3.1.2 (Environmental services room for facility-based environmental services) shall be provided exclusively for the endoscopy procedure suite.

2.9-3.8.15 Fluid Waste Disposal Facilities

Fluid waste disposal facilities shall be located in the endoscopy facility.

2.9-3.8.15.1

In the procedure area, a clinical sink or equivalent equipment in a soiled workroom (see Section 2.9-3.8.12) shall be permitted to meet this requirement.

2.9-3.8.15.2

In the recovery area, a toilet equipped with a bedpan-rinsing device in the patient toilet room referred to in Section 2.9-3.10.2 (Patient Toilet Room) or a separate clinical sink shall be permitted to meet this requirement.

Related Code Sections


2.9-3.8 Specific Requirements for Endoscopy Facilities, Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas
-procedure patient care areas in accordance with Section 2.1-3.8.13.4 (Emergency equipment storage ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas
2.9-3.8.2 Specific Requirements for Endoscopy Facilities, Nurse or Control Station
entering the patient care and diagnostic areas ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas > 2.9-3.8.2 Nurse or Control Station
2.9-3.8.3 Specific Requirements for Endoscopy Facilities, — 2.9-3.8.7 Reserved
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas > 2.9-3.8.3 — 2.9-3.8.7 Reserved
2.9-3.8.8 Specific Requirements for Endoscopy Facilities, Medication Safety Zone
See Section 2.1-3.8.8 (Medication Safety Zones) for requirements ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas > 2.9-3.8.8 Medication Safety Zone
2.9-3.8.9 Specific Requirements for Endoscopy Facilities, — 2.9-3.8.11 Reserved
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.9 Specific Requirements for Endoscopy Facilities > 2.9-3 Patient Care and Diagnostic Areas > 2.9-3.8 Support Areas for the Endoscopy Procedure Area and Other Patient Care Areas > 2.9-3.8.9 — 2.9-3.8.11 Reserved
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING