Where sterile processing services are provided off-site, the following on-site support spaces shall be provided:
2.1-5.1.3.1 A Room for Breakdown (Receiving/Unpacking) of Clean/Sterile Supplies
See Section 2.1-5.1.2.4 (2) (Clean/sterile medical/surgical supply receiving) for requirements.
2.1-5.1.3.2 A Room for On-Site Storage of Clean and Sterile Supplies
See Section 2.1-5.1.2.4 (1) (Instrument and supply storage) for requirements.
2.1-5.1.3.3 A Room With a Flush-Type Device for Gross Decontamination and Holding of Instruments
The soiled workroom described in Section 2.1-2.8.12 (Soiled Workroom or Soiled Holding Room) shall be permitted to serve this purpose.