2.2-3.8 Support Areas for General and Specialty Medical Services Facilities
Go To Full Code Chapter
2.2-3.8.1 — 2.2-3.8.10 Reserved
*2.2-3.8.11 Clean Workroom or Work Area or Clean Supply Room or Area
A clean workroom or a clean supply room shall be provided. Provision of a clean work area or a clean supply area shall be permitted to meet this requirement.
A2.2-3.8.11 Clean supply area. In a small facility, a closet would be acceptable for this purpose.
2.2-3.8.11.1
Where this space is provided for preparing patient care items, the clean workroom or clean work area shall meet the requirements in Section 2.1-3.8.11.2 (Clean workroom).
2.2-3.8.11.2
Where this space is provided only for storage and holding as part of a system for distribution of clean supplies, the clean supply room or clean supply area shall meet the requirements in Section 2.1-3.8.11.3 (Clean supply room).
2.2-3.8.11.3
A clean workroom shall be permitted to be shared with other clinical services in the same building.
2.2-3.8.12 Soiled Holding Room
A soiled holding room that meets the requirements in Section 2.1-3.8.12.3 (Soiled holding room) shall be provided.
*2.2-3.8.13 Equipment and Supply Storage
Storage for equipment and supplies shall be provided.
A2.2-3.8.13 Operational needs and work flows should be considered in sizing and locating storage rooms or areas.
Related Code Sections
2.2-3.8 Specific Requirements for General and Specialty Medical Services Facilities, Support Areas for General and Specialty Medical Services Facilities
this requirement. A2.2-3.8.11 Clean supply area. In a small facility, a closet would be acceptable for this purpose ...
2.2-3.8.11.1 Specific Requirements for General and Specialty Medical Services Facilities,
Where this space is provided for preparing patient care items, the clean workroom or clean work area shall meet the requirements in Section 2.1 ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.2 Specific Requirements for General and Specialty Medical Services Facilities > 2.2-3 Patient Care and Diagnostic Areas > 2.2-3.8 Support Areas for General and Specialty Medical Services Facilities > *2.2-3.8.11 Clean Workroom or Work Area or Clean Supply Room or Area > 2.2-3.8.11.1
2.2-3.8.11.2 Specific Requirements for General and Specialty Medical Services Facilities,
supply area shall meet the requirements in Section 2.1-3.8.11.3 (Clean supply room) ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.2 Specific Requirements for General and Specialty Medical Services Facilities > 2.2-3 Patient Care and Diagnostic Areas > 2.2-3.8 Support Areas for General and Specialty Medical Services Facilities > *2.2-3.8.11 Clean Workroom or Work Area or Clean Supply Room or Area > 2.2-3.8.11.2
2.2-3.1 Specific Requirements for General and Specialty Medical Services Facilities, General
or specialty medical services facility, they shall meet the requirements in Section 2.1-3 as amended in this section ...
2.2-6 Specific Requirements for General and Specialty Medical Services Facilities, Public and Administrative Areas
areas or rooms in general and specialty medical services facilities may require greater seating capacity than that recommended in appendix section 2.1 ...