Section 414 (IFGC) Supplemental and Standby Gas Supply

Fuel Gas Code 2015 of Utah > 4 Gas Piping Installations > 414 (IFGC) Supplemental and Standby Gas Supply
JUMP TO FULL CODE CHAPTER

414.1 Use of Air or Oxygen Under Pressure

Where air or oxygen under pressure is used in connection with the gas supply, effective means such as a backpressure regulator and relief valve shall be provided to prevent air or oxygen from passing back into the gas piping. Where oxygen is used, installation shall be in accordance with NFPA 51.

414.2 Interconnections for Standby Fuels

Where supplementary gas for standby use is connected downstream from a meter or a service regulator where a meter is not provided, a device to prevent backflow shall be installed. A three-way valve installed to admit the standby supply and at the same time shut off the regular supply shall be permitted to be used for this purpose.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 414 Gas Piping Installations, (IFGC) Supplemental and Standby Gas Supply
Where air or oxygen under pressure is used in connection with the gas supply, effective means such as a backpressure regulator and relief valve shall ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 414 (IFGC) Supplemental and Standby Gas Supply
Section 414 Gas Piping Installations, (IFGC) Supplemental and Standby Gas Supply
Where air or oxygen under pressure is used in connection with the gas supply, effective means such as a backpressure regulator and relief valve shall ...
Fuel Gas Code 2015 of Utah > 4 Gas Piping Installations > 414 (IFGC) Supplemental and Standby Gas Supply
Section 401 Gas Piping Installations, (IFGC) General
The storage system for liquefied petroleum gas shall be designed and installed in accordance with the International Fire ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 401 (IFGC) General
Section 409 Gas Piping Installations, (IFGC) Shutoff Valves
with a single dedicated shutoff valve through which all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible ...
Fuel Gas Code 2018 of Utah > 4 Gas Piping Installations > 409 (IFGC) Shutoff Valves
Section 409 Gas Piping Installations, (IFGC) Shutoff Valves
Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall ...
Fuel Gas Code 2015 of Utah > 4 Gas Piping Installations > 409 (IFGC) Shutoff Valves
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US