A supervisory signal that has been deactivated at the protected premises shall comply with 10.14.6.1 and 10.14.6.2.
10.14.6.1
The audible and visible supervisory signal at the control unit only shall automatically reactivate every 24 hours or less until supervisory signal conditions are restored to normal.
10.14.6.2
The audible and visible supervisory signal shall operate until it is manually silenced or acknowledged.