Where required, fire protection systems shall be monitored by an approved supervising station in accordance with NFPA 72.
901.6.1 Automatic Sprinkler Systems
Exceptions:
  1. A supervising station is not required for automatic sprinkler systems protecting one- and two-family dwellings.
  2. Limited area systems in accordance with Section 903.3.8.
[F] 901.6.2 Integrated Testing
Where two or more fire protection or life safety systems are interconnected, the intended response of subordinate fire protection and life safety systems shall be verified when required testing of the initiating system is conducted. In addition, integrated testing shall be performed in accordance with Sections 901.6.2.1 and 901.6.2.2.
[F] 901.6.2.1 High-Rise Buildings
For high-rise buildings, integrated testing shall comply with NFPA 4, with an integrated test performed prior to issuance of the certificate of occupancy and at intervals not exceeding 10 years, unless otherwise specified by an integrated system test plan prepared in accordance with NFPA 4. If an equipment failure is detected during integrated testing, a repeat of the integrated test shall not be required, except as necessary to verify operation of fire protection or life safety functions that are initiated by equipment that was repaired or replaced.
[F] 901.6.2.2 Smoke Control Systems
Where a fire alarm system is integrated with a smoke control system as outlined in Section 909, integrated testing shall comply with NFPA 4, with an integrated test performed prior to issuance of the certificate of occupancy and at intervals not exceeding 10 years, unless otherwise specified by an integrated system test plan prepared in accordance with NFPA 4. If an equipment failure is detected during integrated testing, a repeat of the integrated test shall not be required, except as necessary to verify operation of fire protection or life safety functions that are initiated by equipment that was repaired or replaced.
901.6.3 Fire Alarm Systems
Fire alarm systems required by the provisions of Section 907.2 of this code and Sections 907.2 and 907.9 of the International Fire Code shall be monitored by an approved supervising station in accordance with Section 907.6.6 of this code.
Exceptions:
  1. Single- and multiple-station smoke alarms required by Section 907.2.11.
  2. Smoke detectors in Group I-3 occupancies.
  3. Supervisory service is not required for automatic sprinkler systems in one- and two-family dwellings.
901.6.4 Group H
Supervision and monitoring of emergency alarm, detection and automatic fire-extinguishing systems in Group H occupancies shall be in accordance with the International Fire Code.

Related Code Sections

3.3.293 Definitions, Supervisory Service
The service required to monitor performance of guard tours and the operative condition of fixed suppression systems or other systems ...
901.6 Fire Protection and Life Safety Systems, Supervisory Service
smoke alarms required by Section 907.2.11. Smoke detectors in Group I-3 occupancies. Supervisory service is not required for automatic sprinkler ...
901.6 Fire Protection and Life Safety Systems, Supervisory Service
smoke alarms required by Section 907.2.10. Smoke detectors in Group I-3 occupancies. Supervisory service is not required for automatic sprinkler ...
901.6.3 Fire Protection and Life Safety Systems, Fire Alarm Systems
required by Section 907.2.10. Smoke detectors in Group I-3 occupancies. Supervisory service is not required for automatic sprinkler systems in one ...