N1102.2.13 (R402.2.13) Sunroom Insulation
JUMP TO FULL CODE CHAPTER
Sunrooms enclosing conditioned space shall meet the insulation requirements of this code.
Exception: For sunrooms with thermal isolation, and enclosing conditioned space, the following exceptions to the insulation requirements of this code shall apply:
- The minimum ceiling insulation R-values shall be R-19 in Climate Zones 1 through 4 and R-24 in Climate Zones 5 through 8.
- The minimum wall insulation R-value shall be R-13 in all climate zones. Walls separating a sunroom with a thermal isolation from conditioned space shall comply with the building thermal envelope requirements of this code.
Related Code Sections
N1102.2.13 [RE] Energy Efficiency, (R402.2.13) Sunroom Insulation
Sunrooms enclosing conditioned space shall meet the insulation requirements of this code. Exception: For sunrooms with thermal isolation ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1102 (R402) Building Thermal Envelope > N1102.2 (R402.2) Specific Insulation Requirements (Prescriptive) > N1102.2.13 (R402.2.13) Sunroom Insulation
R402.2.13 [RE] Residential Energy Efficiency, Sunroom Insulation
Sunrooms enclosing conditioned space shall meet the insulation requirements of this code. Exception: For sunrooms with thermal isolation ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R402 Building Thermal Envelope > R402.2 Specific Insulation Requirements (Prescriptive) > R402.2.13 Sunroom Insulation
R301.2.1.1.1 Building Planning, Sunrooms
Sunrooms shall comply with AAMA/NPEA/NSA 2100. For the purpose of applying the criteria of AAMA/NPEA/NSA 2100 based on the intended use, sunrooms ...
Residential Code 2018 of Kansas > 3 Building Planning > R301 Design Criteria > R301.2 Climatic and Geographic Design Criteria > R301.2.1 Wind Design Criteria > R301.2.1.1 Wind Limitations and Wind Design Required > R301.2.1.1.1 Sunrooms
R303.9.1 Building Planning, Sunroom Additions
Required glazed openings shall be permitted to open into sunroom additions or patio covers that abut a street, yard or court if in excess of 40 ...
Residential Code 2018 of Kansas > 3 Building Planning > R303 Light, Ventilation and Heating > R303.9 Required Glazed Openings > R303.9.1 Sunroom Additions
R503.1.1 [RE] Existing Buildings, Building Envelope
Building envelope assemblies that are part of the alteration shall comply with Section R402.1.2 or R402.1.4, Sections R402.2.1 through R402.2.13 ...
Energy Conservation Code 2018 of Kansas > 5 [RE] Existing Buildings > R503 Alterations > R503.1 General > R503.1.1 Building Envelope