The shear values for shear panels of different capacities applied to the same side of the wall are not cumulative except as allowed in Table 2306.4.1.
  The shear values for material of the same type and capacity applied to both faces of the same wall are cumulative. Where the material capacities are not equal, the allowable shear shall be either two times the smaller shear capacity or the capacity of the stronger side, whichever is greater. Summing shear capacities of dissimilar materials applied to opposite faces or to the same wall line is not allowed.
  Exception: For wind design, the allowable shear capacity of shear wall segments sheathed with a combination of wood structural panels and gypsum wallboard on opposite faces, fiberboard structural sheathing and gypsum wall board on opposite faces or hardboard panel siding and gypsum wallboard on opposite faces shall equal the sum of the sheathing capacities of each face separately.

Related Code Sections

2305.3.8 Wood, Summing Shear Capacities
is greater. Summing shear capacities of dissimilar materials applied to opposite faces or to the same wall line is not allowed.   Exception ...
2306.3.1 Wood, Shear Capacities Modifications
The allowable shear capacities in Table 2306.3.1 for horizontal wood structural panel diaphragms shall be increased 40 percent for wind design.  ...
22.5.10.4 Sectional Strength,
If more than one type of shear reinforcement is provided to reinforce the same portion of a member, Vs shall be the sum of the Vs values ...
1908.2 Concrete, General
resisting earthquake effect shall not be less than either 1 or 2: The sum of the shear associated with development of nominal moment strengths ...