12-7A-1.5 Summary of Test Method
JUMP TO FULL CODE CHAPTER
- Direct flame exposure. This test method provides for the direct flame exposure of a wall specimen to a flame source centered at the base of a 4-foot by 8-foot (1220 mm by 2440 mm) test assembly.
- Gas burner. The method employs a gas burner to produce a diffusion flame in contact with the test wall assembly.
- Heat output. The gas burner produces a prescribed net rate of heat output of 8535 Btu/min (150 kW) for a period of 10 minutes, after which the flame exposure is terminated.
- Resistance to fire penetration. The test method measures the ability of the wall system to resist fire penetration from the exterior to the unexposed side of the test assembly under the conditions of exposure. Observations are made for the appearance of sustained flaming or glow on the unexposed side and/or sustained glowing on the unexposed side at the end of a 60-minute observation period.
Related Code Sections
12-7A-1.5 Materials and Construction Methods for Exterior Wildfire Exposure, Summary of Test Method
Direct flame exposure. This test method provides for the direct flame exposure of a wall specimen to a flame source centered at the base of a 4-foot ...
California Referenced Standards Code 2016 > 12-7A Materials and Construction Methods for Exterior Wildfire Exposure > 12-7A-1.5 Summary of Test Method
12-7A-1.5 Materials and Construction Methods for Exterior Wildfire Exposure, Summary of Test Method
Direct flame exposure. This test method provides for the direct flame exposure of a wall specimen to a flame source centered at the base of a 4-foot ...
California Referenced Standards Code 2019 > 12-7A Materials and Construction Methods for Exterior Wildfire Exposure > 12-7A-1.5 Summary of Test Method
Section 12-8-105 Fire-Resistive Standards for Fire Protection,
Summary of method. The test involves an ignition source exposure of the wall, ceiling and/or floor lining materials or assemblies as they would ...
California Referenced Standards Code 2016 > 12-8-1 Fire-Resistive Standards for Fire Protection > 12-8-105
Section 12-8-105 Fire-Resistive Standards for Fire Protection,
Summary of method. The test involves an ignition source exposure of the wall, ceiling and/or floor lining materials or assemblies as they would ...
California Referenced Standards Code 2019 > 12-8-1 Fire-Resistive Standards for Fire Protection > 12-8-105
23.3.5.2 Plans and Calculations, Summary Sheet
The summary sheet as shown in Figure 23.3.5.1.2(a) shall contain the following information, where applicable: Project name and date Location ...
Standard for the Installation of Sprinkler Systems 2016 of California > 23 Plans and Calculations > 23.3 Hydraulic Calculation Forms > 23.3.5 Hydraulic Reports > 23.3.5.2 Summary Sheet