Areas other than patient sleeping areas in Group I-2 occupancies shall be permitted to be divided into suites.
1014.2.4.1 Area
Suites of rooms, other than patient sleeping rooms, shall not exceed 10,000 square feet (929 m2).
1014.2.4.2 Exit Access
Any room or suite of rooms, other than patient sleeping rooms, of more than 2,500 square feet (232 m2) shall have at least two exit access doors remotely located from each other.
1014.2.4.3 One Intervening Room
For rooms other than patient sleeping rooms, suites of rooms are permitted to have one intervening room if the travel distance within the suite to the exit access door is not greater than 100 feet (30 480 mm).
1014.2.4.4 Two Intervening Rooms
For rooms other than patient sleeping rooms located within a suite, exit access travel from within the suite shall be permitted through two intervening rooms where the travel distance to the exit access door is not greater than 50 feet (15 240 mm).