Section 512 Subslab Soil Exhaust Systems
JUMP TO FULL CODE CHAPTER
Where a subslab soil exhaust system is provided, the duct shall conform to the requirements of this section.
Subslab soil exhaust system duct material shall be air duct material listed and labeled to the requirements of UL 181 for Class 0 air ducts, or any of the following piping materials that comply with the International Plumbing Code as building sanitary drainage and vent pipe: cast iron; galvanized steel; copper or copper-alloy pipe and tube of a weight not less than type DWV; and plastic piping.
Exhaust system ducts shall not be trapped and shall have a minimum slope of one-eighth unit vertical in 12 units horizontal (1-percent slope).
Subslab soil exhaust system ducts shall extend through the roof and terminate not less than 6 inches (152 mm) above the roof and not less than 10 feet (3048 mm) from any operable openings or air intake.
Related Code Sections
Section 512 Exhaust Systems, Subslab Soil Exhaust Systems
Where a subslab soil exhaust system is provided, the duct shall conform to the requirements of this section ...
501.1 Exhaust Systems, Scope
and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy ...
401.1 Ventilation, Scope
serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke ...
501.3.1 Exhaust Systems, Location of Exhaust Outlets
and other kitchen exhaust equipment , Sections 506.3.13, 506.4 and 506.5. 5.3. Dust, stock and refuse conveying systems, Section 511.2. 5.4. Subslab ...
Mechanical Code 2018 of Maryland > 5 Exhaust Systems > 501 General > 501.3 Exhaust Discharge > 501.3.1 Location of Exhaust Outlets
Section 501 Exhaust Systems, General
and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy ...