503.1 Water Depth
The maximum water depth for spas shall be 4 feet (1219 mm) measured from the design waterline except for spas that are designed for special purposes and approved by the authority having jurisdiction. The water depth for exercise spas shall not exceed 6 feet 6 inches (1981 mm) measured from the design waterline.
503.2 Multilevel Seating
Where multilevel seating is provided, the maximum water depth of any seat or sitting bench shall be 28 inches (711 mm) measured from the design waterline to the lowest measurable point.
503.3 Floor Slope
The slope of the floor shall not exceed 1 unit vertical in 12 units horizontal (8.3-percent slope). Where multilevel floors are provided, the change in depth shall be indicated.

Related Code Sections

Section 503 Public Spas and Public Exercise Spas, Structure and Design
The maximum water depth for spas shall be 4 feet (1219 mm) measured from the design waterline except for spas that are designed for special purposes ...
Section 503 Public Spas and Public Exercise Spas, Structure and Design
The maximum water depth for spas shall be 4 feet (1219 mm) measured from the design waterline except for spas that are designed for special purposes ...
1406.4 Exterior Walls, Structural Design
MCM systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding ...
1407.3 Exterior Walls, Structural Design
The underlying structural framing and substrate shall be designed and constructed to resist loads as required by Chapter 16 ...
1407.4 Exterior Walls, Structural Design
MCM systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding ...