Section 1708 Structural Testing Forseismic Resistance

Jump To Full Code Chapter
1708.1 Testing and Qualification for Seismic Resistance
The testing and qualification specified in Sections 1708.2 through 1708.5, unless exempted from special inspections by the exceptions of Section 1704.1, 1705.3 or 1705.3.1 are required as follows:
  1. The seismic-force-resisting systems in structures assigned to Seismic Design Category C, D, E or F, as determined in Section 1613 shall meet the requirements of Sections 1708.2 and 1708.3, as applicable.
  2. Designated seismic systems in structures assigned to Seismic Design Category C, D, E or F subject to the special certification requirements of ASCE 7 Section 13.2.2 are required to be tested in accordance with Section 1708.4.
  3. Architectural, mechanical and electrical components in structures assigned to Seismic Design Category C, D, E or F with an Ip = 1.0 are required to be tested in accordance with Section 1708.4 where the general design requirements of ASCE 7 Section 13.2.1, Item 2 for manufacturer's certification are satisfied by testing.
  4. The seismic isolation system in seismically isolated structures shall meet the testing requirements of Section 1708.5.
1708.2 Concrete Reinforcement
Where reinforcement complying with ASTM A 615 is used to resist earthquake-induced flexural and axial forces in special moment frames, special structural walls and coupling beams connecting special structural walls, in structures assigned to Seismic Design Category B, C, D, E or F as determined in Section 1613, the reinforcement shall comply with Section 21.1.5.2 of ACI 318. Certified mill test reports shall be provided for each shipment of such reinforcement. Where reinforcement complying with ASTM A 615 is to be welded, chemical tests shall be performed to determine weldability in accordance with Section 3.5.2 of ACI 318.
1708.3 Structural Steel
Testing for structural steel shall be in accordance with the quality assurance plan requirements of AISC 341.
Exceptions:
  1. Testing for structural steel in structures assigned to Seismic Design Category C that are not specifically detailed for seismic resistance, with a response modification coefficient, R, of 3 or less, excluding cantilever column systems.
  2. For ordinary moment frames, ultrasonic and magnetic particle testing of complete joint penetration groove welds are only required for demand critical welds.
1708.4 Seismic Certification of Nonstructural Components
The registered design professional shall state the applicable seismic certification requirements for nonstructural components and designated seismic systems on the construction documents.
  1. The manufacturer of each designated seismic system component subject to the provisions of ASCE 7 Section 13.2.2 shall test or analyze the component and its mounting system or anchorage and submit a certificate of compliance for review and acceptance by the registered design professional responsible for the design of the designated seismic system and for approval by the building official. Certification shall be based on an actual test on a shake table, by three-dimensional shock tests, by an analytical method using dynamic characteristics and forces, by the use of experience data (i.e., historical data demonstrating acceptable seismic performance) or by more rigorous analysis providing for equivalent safety.
  2. Manufacturer's certification of compliance for the general design requirements of ASCE 7 Section 13.2.1 shall be based on analysis, testing or experience data.
1708.5 Seismically Isolated Structures
For required system tests, see Section 17.8 of ASCE 7.

Related Code Sections

Section 1708 Structural Tests and Special Inspections, Structural Testing Forseismic Resistance
1704.1, 1705.3 or 1705.3.1 are required as follows: The seismic-force-resisting systems in structures assigned to Seismic Design Category C, D, E or F ...
1707.3 Structural Tests and Special Inspections, Structural Wood
Continuous special inspection is required during field gluing operations of elements of the seismic-force-resisting system. Periodic special ...
1707.2 Structural Tests and Special Inspections, Structural Steel
inspections of structural steel in structures assigned to Seismic Design Category C that are not specifically detailed for seismic resistance ...
1707.1 Structural Tests and Special Inspections, Special Inspections for Seismic Resistance
, are required for the following: The seismic-force-resisting systems in structures assigned to Seismic Design Category C, D, E or F, as determined in Section ...
1707.7 Structural Tests and Special Inspections, Mechanical and Electrical Components
of electrical equipment for emergency or standby power systems in structures assigned to Seismic Design Category C, D, E or F; Periodic special inspection ...