1617.6 Structural Peer Review Report
JUMP TO FULL CODE CHAPTER
The reviewing engineer shall submit a report to the department stating whether or not the structural design shown on the plans and specifications generally conforms to the structural and foundation requirements of this code.
The report shall demonstrate, at a minimum, compliance with Items 1 through 11 of Section 1617.5.1. In addition, the report shall also include the following:
- The codes and standards used in the structural design of the project.
- The structural design criteria, including loads and performance requirements.
- The basis for design criteria that are not specified directly in applicable codes and standards. This should include reports by specialty consultants such as wind tunnel study reports and geotechnical reports. Generally, the report should confirm that existing conditions at the site have been investigated as appropriate and that the design of the proposed structure is in general conformance with these conditions.
If an application is submitted for a permit for the construction of foundations or any other part of a building before the construction documents for the whole building have been submitted, then the structural peer review and report shall be phased. The structural peer reviewer shall be provided with sufficient information on which to make a structural peer review of the phased submission.
Related Code Sections
1617.6 Structural Design, Structural Peer Review Report
, then the structural peer review and report shall be phased. The structural peer reviewer shall be provided with sufficient information on which to make ...
NYC Building Code 2014 > 16 Structural Design > 1617 Structural Peer Review > 1617.6 Structural Peer Review Report
1627.7 Structural Design, Structural Peer Review Report
have been submitted, then the structural peer review and report shall be phased. The structural peer reviewer shall be provided with sufficient ...
NYC Building Code 2008 > 16 Structural Design > 1627 Structural Peer Review > 1627.7 Structural Peer Review Report
1627.7.3 Structural Design, Phased Submission
for the whole building have been submitted, then the structural peer review and report shall be phased. The structural peer reviewer shall ...
NYC Building Code 2008 > 16 Structural Design > 1627 Structural Peer Review > 1627.7 Structural Peer Review Report > 1627.7.3 Phased Submission
1617.7 Structural Design, Responsibility
standard of care to which the structural peer reviewer shall be held in the performance of the structural peer review and report is that the level of skill ...
1627.8 Structural Design, Responsibility
of the structural peer reviewer shall not relieve the structural engineer of record of this responsibility ...