1704.6.2 Structural Observations for Wind Requirements
JUMP TO FULL CODE CHAPTER
Structural observations shall be provided for those structures sited where Vasd as determined in accordance with Section 1609.3.1 exceeds 110 mph (49 m/sec), where one or more of the following conditions exist:
- The structure is classified as Risk Category III or IV.
- The building height is greater than 75 feet (22 860 mm).
- When so designated by the registered design professional responsible for the structural design.
- When such observation is specifically required by the building official.
Related Code Sections
1710.3 Structural Tests and Special Inspections, Structural Observations for Wind Requirements
Structural observations shall be provided for those structures sited where the basic wind speed exceeds 110 mph (49 m/sec) determined from Figure ...
Building Code 2009 of Alabama > 17 Structural Tests and Special Inspections > 1710 Structural Observations > 1710.3 Structural Observations for Wind Requirements
1704.6.2 Special Inspections and Tests, Structural Observations for Wind Requirements
Structural observations shall be provided for those structures sited where V asd as determined in accordance with Section 1609.3.1 exceeds 110 mph ...
Building Code 2015 of Alabama > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.6 Structural Observations > 1704.6.2 Structural Observations for Wind Requirements
Section 1702 Structural Tests and Special Inspections, Definitions
An assemblage of structural elements assigned to provide support and stability for the overall structure. The system generally receives wind ...
Section 1704 Special Inspections and Tests, Special Inspections and Tests, Contractor Responsibility and Structural Observation
and structural observations shall meet the applicable requirements of this section ...
Building Code 2015 of Alabama > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation
1702.1 Structural Tests and Special Inspections, General
An assemblage of structural elements assigned to provide support and stability for the overall structure. The system generally receives wind ...
Building Code 2009 of Alabama > 17 Structural Tests and Special Inspections > 1702 Definitions > 1702.1 General