Guards with structural glass baluster panels shall be installed with an attached top rail or handrail. The top rail or handrail shall be supported by not fewer than three glass baluster panels, or shall be otherwise supported to remain in place should one glass baluster panel fail.
Exception: An attached top rail or handrail is not required where the glass baluster panels are laminated glass with two or more glass plies of equal thickness and of the same glass type. The panels shall be tested to remain in place as a barrier following impact or glass breakage in accordance with ASTM E2353.

Related Code Sections

2407.1.2 Glass and Glazing, Structural Glass Baluster Panels
Guards with structural glass baluster panels shall be installed with an attached top rail or handrail. The top rail or handrail shall be supported ...
2406.4.4 Glass and Glazing, Glazing in Guards and Railings
Glazing in guards and railings, including structural baluster panels and nonstructural in-fill panels, regardless of area or height above a walking ...
2406.4.4 Glass and Glazing, Glazing in Guards and Railings
Glazing in guards and railings, including structural baluster panels and nonstructural in-fill panels, regardless of area or height above a walking ...
2407.1.2 Glass and Glazing, Guards With Structural Glass Balusters
Guards with structural glass balusters, whether vertical posts, columns or panels, shall be installed with an attached top rail or handrail ...