8.7.6 Strainers
Go To Full Code Chapter
A listed strainer shall be provided in the riser or feed main that supplies sprinklers having nominal K-factors smaller than K-2.8 (40).
Upcodes Diagrams
Related Code Sections
22.21.2.6 Special Occupancy Requirements, Strainers
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3/8 in. (9.5 mm) diameter. [214:5.2.7] ...
22.21.2.7 Special Occupancy Requirements, Strainers
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3/8 in. (9.5 mm) diameter. [214:5.2.7] ...
26.21.2.6 Special Occupancy Requirements, Strainers
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3/8 in. (9.5 mm) diameter. [214:5.2.7] ...
7.10.10 System Requirements, Strainers
A listed line strainer shall be installed in the main water supply preceding sprinklers or automatic spray nozzles having nominal K-factors smaller ...
7.7.6 System Requirements, Strainers
A listed strainer shall be provided in the riser or feed main that supplies sprinklers having nominal K-factors smaller than K-2.8 (40) ...