1926.152(c)(1)
Storage of containers (not more than 60 gallons each) shall not exceed 1,100 gallons in any one pile or area. Piles or groups of containers shall be separated by a 5-foot clearance. Piles or groups of containers shall not be nearer than 20 feet to a building.
1926.152(c)(2)
Within 200 feet of each pile of containers, there shall be a 12-foot-wide access way to permit approach of fire control apparatus.
1926.152(c)(3)
The storage area shall be graded in a manner to divert possible spills away from buildings or other exposures, or shall be surrounded by a curb or earth dike at least 12 inches high. When curbs or dikes are used, provisions shall be made for draining off accumulations of ground or rain water, or spills of flammable liquids. Drains shall terminate at a safe location and shall be accessible to operation under fire conditions.
1926.152(c)(4) Outdoor Portable Tank Storage
1926.152(c)(4)(i)
Portable tanks shall not be nearer than 20 feet from any building. Two or more portable tanks, grouped together, having a combined capacity in excess of 2,200 gallons, shall be separated by a 5-foot-clear area. Individual portable tanks exceeding 1,100 gallons shall be separated by a 5-foot-clear area.
1926.152(c)(4)(ii)
Within 200 feet of each portable tank, there shall be a 12-foot-wide access way to permit approach of fire control apparatus.
1926.152(c)(5)
Storage areas shall be kept free of weeds, debris, and other combustible material not necessary to the storage.
1926.152(c)(6)
Portable tanks, not exceeding 660 gallons, shall be provided with emergency venting and other devices, as required by chapters III and IV of NFPA 30-1969, The Flammable and Combustible Liquids Code.
1926.152(c)(7)
Portable tanks, in excess of 660 gallons, shall have emergency venting and other devices, as required by chapters II and III of The Flammable and Combustible Liquids Code, NFPA 30-1969.

Related Code Sections

1926.152(c) Fire Protection and Prevention, Storage Outside Buildings
storage area shall be graded in a manner to divert possible spills away from buildings or other exposures, or shall be surrounded by a curb or earth dike ...
1926.153(k) Fire Protection and Prevention, Storage Outside of Buildings
Storage outside of buildings, for containers awaiting use, shall be located from the nearest building or group of buildings, in accordance ...
1926.152(c)(6) Fire Protection and Prevention,
Portable tanks, not exceeding 660 gallons, shall be provided with emergency venting and other devices, as required by chapters III and IV of NFPA 30 ...
1926.152(c)(7) Fire Protection and Prevention,
Portable tanks, in excess of 660 gallons, shall have emergency venting and other devices, as required by chapters II and III of The Flammable ...
1926.152(c)(4)(i) Fire Protection and Prevention,
Portable tanks shall not be nearer than 20 feet from any building. Two or more portable tanks, grouped together, having a combined capacity in excess ...