Loose combustible fibers in quantities exceeding 100 cubic feet (3 m3) but not exceeding 500 cubic feet (14 m3) shall be stored in rooms enclosed with 1-hour fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both, with openings protected by an approved opening protective assembly having a fire protection rating of 3/4 hour in accordance with the International Building Code.
Upcodes Diagrams

Related Code Sections

3704.3 Combustible Fibers, Storage of More Than 100 Cubic Feet to 500 Cubic Feet
Loose combustible fibers in quantities exceeding 100 cubic feet (3 m3) but not exceeding 500 cubic feet (14 m3) shall be stored in rooms enclosed ...
3704.3 Combustible Fibers, Storage of More Than 100 Cubic Feet to 500 Cubic Feet
Loose combustible fibers in quantities exceeding 100 cubic feet (3 m3) but not exceeding 500 cubic feet (14 m3) shall be stored in rooms enclosed ...
6604.1.4 Unstable (Reactive) Materials, Storage Configuration
Unstable (reactive) materials stored in quantities greater than 500 cubic feet (14 m3) shall be separated into piles, each not larger than 500 cubic ...
6604.1.4 Unstable (Reactive) Materials, Storage Configuration
Unstable (reactive) materials stored in quantities greater than 500 cubic feet (14 m3) shall be separated into piles, each not larger than 500 cubic ...
3704.2 Combustible Fibers, Storage of 100 Cubic Feet or Less
Loose combustible fibers in quantities of not more than 100 cubic feet (3 m3) located in a structure shall be stored in a metal or metal-lined bin ...