• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

§4838-01 Storage of Liquefied Petroleum Gases in Pre-Existing Facilities

Title 3 ‒ Fire Department > 48 Pre-Existing Facilities > §4838-01 Storage of Liquefied Petroleum Gases in Pre-Existing Facilities
JUMP TO FULL CODE CHAPTER
   (a)   Scope. This section consolidates the Fire Prevention Code and former Fire Department rules in effect on June 30, 2008, that are applicable to the design and installation of pre-existing liquefied petroleum gases storage facilities.
   (b)   Definitions. Reserved
   (c)   Facilities in Compliance With Former Fire Department Rules in Effect on June 30, 2008. LPG storage facilities in compliance with former Fire Department rule 3 RCNY §25-01 in effect on June 30, 2008 are allowed and would be approved under the provisions of the Fire Code and the rules, and accordingly, such facilities shall be designed and installed in compliance with the requirements of FC Chapter 38 and the R3809-01, except that where the storage facility clearance distances from building openings; stationary LPG installations clearance distances from building openings, lot lines, buildings on an adjoining lots, sidewalks, motor vehicles, and vent and fill lines of flammable or combustible liquid storage tanks; and previously exempt storage and use (as set forth in 3 RCNY §25-01(k)); of such outdoor storage facility are lawfully not in compliance with the requirements of such chapter and rule, such pre-existing conditions shall be continued in compliance with the provisions of former Fire Department rule 3 RCNY §25-01(g), (i) and (k), as applicable, until such time such facilities may be required to comply with the design and installation requirements of the Fire Code and rules with respect to such conditions.
      (1)   Former Fire Department Rule 3 RCNY §25-01(g), (i) and (k)
         §25-01 Storage and Use of Liquefied Petroleum Gases.
         (g)   Outdoor storage facilities.
. . . . . . . . . .
         (4)   No outdoor storage facility shall be located within:
         (i)   five (5) feet of any building opening, including any door, openable window, intake or exhaust vent;
. . . . . . . . . .
         (i)   Stationary LPG installations.
. . . . . . . . . .
         (7)   No LPG container connected for use shall be located within:
         (i)   five (5) feet of any building opening, including any door, openable window or intake or exhaust vent;
         (ii)   five (5) feet of the nearest lot line, sidewalk or building on an adjoining lot . . . . . ;
         (iii)   five (5) feet of any parked motor vehicle;
         (iv)   five (5) feet of any vent or fill line of any flammable or combustible liquid storage tank;
. . . . . . . . . .
         (k)   Pre-existing storage and use.
         (1)   Exemptions. Subject to the provisions of paragraph (2) of this subdivision, LPG storage and use in or for the following existing facilities and installations shall be maintained and operated in accordance with the original approval conditions and the provisions of this section, except as follows:
         (i)   The provisions of paragraph (5) of subdivision (f) and paragraph (7) of subdivision (i) of this section shall not apply to any stationary LPG installation that was issued a Department permit prior to the effective date of this section, including the stationary LPG installations described in paragraph (7) of subdivision (j) and subparagraphs (ii), (iii) and (iv) of this paragraph.
         (ii)   The provisions of paragraph (5) of subdivision (c) and paragraph (5) of subdivision (i) of this section shall not apply to a LPG container installation in a residential occupancy that was issued a Department permit prior to the effective date of this section.
         (iii)   The provisions of paragraph (13) of subdivision (c) of this section shall not apply to LPG storage and use for non-residential space heating or water heating when a Department permit for such storage and use was issued prior to the effective date of this section.
         (iv)   The provisions of paragraphs (8) and (10) of subdivision (c) and paragraph (5) of subdivision (f) of this section shall not apply to a roof-mounted emergency generator installation that was issued a Department permit prior to the effective date of this section.
         (v)   The provisions of subdivision (g) and paragraph (5) of subdivision (f) of this section shall not apply to an outdoor LPG storage facility that was issued a Department permit prior to the effective date of this section.
         (vi)   The provisions of item (iii) of paragraph (2) of subdivision (h) and paragraph (4) of subdivision (h) of this section shall not apply to an indoor LPG storage facility that was issued a Department permit prior to the effective date of this section.
         (2)   Discontinuance of exempt storage and use.
         (i)   The LPG storage and use authorized by subparagraphs (1)(i), (ii), (iii) and (iv) of this subdivision shall be discontinued and all LPG containers removed from the premises: (A)  by December 31, 2004, if access to natural gas from a public utility is available on the effective date of this rule; or
         (B)   within five years after access to natural gas from a public utility becomes available, if such access is not available on the effective date of this rule.
         (ii)   Notwithstanding any other provision of this subdivision, the Department may require any facility or installation granted an exemption by this subdivision to comply with all applicable provisions of this section and may require discontinuance and removal of any facility or installation not in compliance with the provisions of this section, where the Department finds that such facility or installation has been operated contrary to the original approval conditions or poses an undue danger to public safety.   Provisions Referenced in §25-01(k)
         (c)   General prohibitions.
. . . . . . . . . .
         (5)   store or use in, or bring or allow into, any residential occupancy or on any lot containing a building used for a residential occupancy, any LPG container with a capacity greater than sixteen and four tenths ounces (16.4 oz.), except as provided in subdivision (j) and (k) of this section.
. . . . . . . . . .
         (8)   use on the roof of any building any LPG container with a capacity greater than sixteen and four tenths ounces (16.4 oz.), except as provided in subdivisions (j) and (k) of this section.
. . . . . . . . . .
         (10)   store or use LPG for a stationary installation in any area where access to natural gas from a public utility is available, except as provided in subdivision (k) of this section.
. . . . . . . . . .
         (13)   store or use LPG for space heating or water heating, except as provided in subdivisions (j) and (k) of this section.
. . . . . . . . . .
         (f)   General storage and use.
. . . . . . . . . .
         (5)   Storage and use of LPG in quantities exceeding twenty five hundred (2,500) standard cubic feet of gas (approximately 300 pounds) constitutes a high hazard occupancy as set forth in Article 3 of Subchapter 3 of the New York City Building Code. Any such quantities of LPG shall be stored and used in compliance with the Building Code requirements applicable to high hazard occupancies, except as provided in subdivision (k) of this section.
. . . . . . . . . .
         (g)   Outdoor storage facilities.
         (1)   Except as otherwise provided in this section, all LPG containers shall be stored outdoors in a facility that conforms to the requirements of this subdivision. All outdoor LPG storage facilities shall be:
         (i)   not more than fifty four (54) square feet in area;
         (ii)   protected from vehicle impact;
         (iii)   protected from theft, tampering or unauthorized use by a metal open fence enclosure at least six (6) feet in height, secured by a locked gate opening outward, or by a lockable ventilated metal locker of a type for which a Certificate of Approval has been issued by the Department. Such fence enclosure or locker shall be mounted on and secured to a substantial concrete pad at grade level, which pad shall be constructed to prevent accumulation of rain and snow;
         (iv)   located in a well ventilated area. There shall be a minimum clearance of ten (10) feet from any surrounding walls more than eight (8) feet high on at least three sides of the outdoor storage facility;
         (v)   directly accessible from the street. LPG containers being delivered to or taken from an outdoor storage location shall not be brought into or through any building or other structure; and
         (vi)   equipped with at least one 10-B-C rated fire extinguisher in a protective enclosure. Such fire extinguisher shall be affixed to the outside of the storage facility or placed at another readily accessible location not more than thirty (30) feet from the facility.
         (2)   No more than twenty five hundred (2,500) standard cubic feet of LPG (approximately 300 pounds) shall be stored in an outdoor LPG storage facility.
         (3)   No outdoor storage facility shall be located on a lot containing any building used for residential purposes.
         (4)   No outdoor storage facility shall be located within:
         (i)   five (5) feet of any building opening, including any door, openable window, intake or exhaust vent;
         (ii)   ten (10) feet of the nearest lot line, sidewalk or building on an adjoining lot, except as follows:
         (A)   twenty (20) feet of any building of wood frame construction;
         (B)   fifty (50) feet from any building occupied as a multiple dwelling; and
         (C)   one hundred (100) feet of the lot line of any property occupied for educational, health care or religious purposes, place of public assembly, or other place of public gathering;
         (iii)   ten (10) feet of any parked motor vehicle;
         (iv)   ten (10) feet of any combustible material;
         (v)   fifteen (15) feet of any vent or fill line of any flammable or combustible liquid storage tank;
         (vi)   twenty (20) feet of flammable gas storage;
         (vii)   twenty (20) feet of any aboveground flammable or combustible liquid storage tank; and
         (viii)   one hundred (100) feet of any subway entrance or exit, vent or other opening.
. . . . . . . . . .
         (h)   Indoor LPG storage.
. . . . . . . . . .
         (2)   All indoor storage of LPG with an individual capacity greater than sixteen and four tenths ounces (16.4 oz.) authorized by this rule shall be stored in a separate room that conforms to the requirements of this subdivision. Any such room shall be:
. . . . . . . . . .
         (iii)   constructed with an access door that opens directly to the outdoors:
. . . . . . . . . .
         (4)   all delivery and pick-up of containers to or from an indoor LPG storage facility shall be through the outdoors access door only, not through the building.
. . . . . . . . . .
         (i)   Stationary LPG installations.
. . . . . . . . . .
         (5)   When LPG is piped indoors, a sign at least ten (10) inches high and fourteen (14) inches wide shall be conspicuously posted at the entrance to the building and shall bear the wording "Danger-LPG Piping".
. . . . . . . . . .
         (7)   No LPG container connected for use shall be located within:
         (i)   five (5) feet of any building opening, including any door, openable window or intake or exhaust vent;
         (ii)   five (5) feet of the nearest lot line, sidewalk or building on an adjoining lot, except as follows:
         (A)   ten (10) feet of any building of wood frame construction;
         (B)   fifty (50) feet from any building occupied as a multiple dwelling; and
         (C)   one hundred (100) feet of the lot line of any property occupied for educational, health care or religious purposes, place of public assembly, or other place of public gathering;
         (iii)   five (5) feet of any parked motor vehicle;
         (iv)   five (5) feet of any vent or fill line of any flammable or combustible liquid storage tank;
         (v)   ten (10) feet of any combustible material;
         (vi)   twenty (20) feet of any flammable gas storage;
         (vii)   twenty (20) feet of any aboveground flammable or combustible liquid storage tank; and
         (viii)   one hundred (100) feet of any subway entrance, exit, vent or other opening.
. . . . . . . . . .
         (j)   Special storage and use.
. . . . . . . . . .
         (7)   Commercial establishments. Commercial establishments which store and use LPG for cooking and oil burner ignition shall comply with the following requirements:
         (i)   LPG storage and use shall be limited to LPG containers with a capacity not greater than 16.4 ounces unless the container is connected for use in a stationary installation.
         (ii)   All LPG appliances and equipment shall be installed by a plumber licensed by the New York City Department of Buildings.
         (iii)   Rigid piping shall be used for all connections between LPG appliances and equipment and LPG containers.
         (iv)   LPG storage and use for the purposes authorized by this paragraph is subject to the prohibition set forth in paragraph (10) of subdivision (c) of this section, and shall be discontinued in accordance with the provisions of paragraph (2) of subdivision (k) of this section.

Related Code Sections


415.6.3 Special Detailed Requirements Based on Use and Occupancy, Liquefied Petroleum Gas-Distribution Facilities
The construction and installation of liquefied petroleum gas facilities shall be in accordance with the requirements of this code, the New York City ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.6 Group H-2 > 415.6.3 Liquefied Petroleum Gas-Distribution Facilities
415.7.3 Special Detailed Requirements Based on Use and Occupancy, Liquefied Petroleum Gas-Distribution Facilities
Propane, butane, propylene, butylene and other liquefied petroleum gas-distribution facilities shall conform to the provisions of the New York City ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.7 Group H-2 > 415.7.3 Liquefied Petroleum Gas-Distribution Facilities
415.9.2 Special Detailed Requirements Based on Use and Occupancy, Liquefied Petroleum Gas-Distribution Facilities
The construction and installation of liquefied petroleum gas facilities shall be in accordance with the requirements of this code, the New York City ...
NYC Building Code 2022 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.9 Group H-2 > 415.9.2 Liquefied Petroleum Gas-Distribution Facilities
§27-981.1 Fire Alarm, Detection and Extinguishing Equipment, Definitions
For the purpose of this article: "Fossil fuel" shall mean coal, kerosene, oil, wood, fuel gases and other petroleum products. "Fuel gases ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 7 Carbon Monoxide Detecting Devices > §27-981.1 Definitions
403.9.3 Gas Piping Installations, Thread Compounds
Thread (joint) compounds (pipe dope) shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases ...
NYC Fuel Gas Code 2008 > 4 Gas Piping Installations > 403 Piping Materials > 403.9 Metallic Pipe Threads > 403.9.3 Thread Compounds
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING