Section 5304 Storage of Compressed Gases

California Fire Code 2016 > 53 Compressed Gases > 5304 Storage of Compressed Gases
JUMP TO FULL CODE CHAPTER

5304.1 Upright storage

Compressed gas containers, cylinders and tanks, except those designed for use in a horizontal position, and all compressed gas containers, cylinders and tanks containing nonliquefied gases, shall be stored in an upright position with the valve end up. An upright position shall include conditions where the container, cylinder or tank axis is inclined as much as 45 degrees (0.80 rad) from the vertical.

Exceptions:

  1. Compressed gas containers with a water volume less than 1.3 gallons (5 L) are allowed to be stored in a horizontal position.
  2. Cylinders, containers and tanks containing nonflammable gases, or cylinders, containers and tanks containing nonliquefied flammable gases that have been secured to a pallet for transportation purposes.

5304.2 Material-specific regulations

In addition to the requirements of this section, indoor and outdoor storage of compressed gases shall comply with the material-specific provisions of Chapters 54, 58 and 60 through 67.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 5304 Compressed Gases, Storage of Compressed Gases
, indoor and outdoor storage of compressed gases shall comply with the material-specific provisions of Chapters 54, 58 and 60 through 67 ...
California Fire Code 2016 > 53 Compressed Gases > 5304 Storage of Compressed Gases
1910.253(b)(1)(i) Welding, Cutting, and Brazing,
All portable cylinders used for the storage and shipment of compressed gases shall be constructed and maintained in accordance with the regulations ...
OSHA 1910 General Industry > Q Welding, Cutting, and Brazing > 1910.253 Oxygen-fuel gas welding and cutting > 1910.253(b) Cylinders and containers > 1910.253(b)(1) Approval and marking > 1910.253(b)(1)(i)
1910.101(b) Hazardous Materials, Compressed gases
The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.101 Compressed gases (general requirements) > 1910.101(b) Compressed gases
5003.9.8 Hazardous Materials—general Provisions, Separation of incompatible materials
storage cabinets. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with Sections 5003.8.5 and 5003.8.6. Materials ...
California Fire Code 2016 > 50 Hazardous Materials—general Provisions > 5003 General Requirements > 5003.9 General safety precautions > 5003.9.8 Separation of incompatible materials
1926.350(a)(12) Welding and Cutting,
The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks ...
OSHA 1926 Construction > J Welding and Cutting > 1926.350 Gas welding and cutting > 1926.350(a) Transporting, moving, and storing compressed gas cylinders > 1926.350(a)(12)
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US