1910.109(i)(3) Storage of Ammonium Nitrate in Bags, Drums, or Other Containers
JUMP TO FULL CODE CHAPTER
Bags and containers used for ammonium nitrate must comply with specifications and standards required for use in interstate commerce (see 49 CFR Chapter I).
Containers used on the premises in the actual manufacturing or processing need not comply with provisions of paragraph (i)(3)(i)(a) of this paragraph.
Containers of ammonium nitrate shall not be accepted for storage when the temperature of the ammonium nitrate exceeds 130 deg. F.
Bags of ammonium nitrate shall not be stored within 30 inches of the storage building walls and partitions.
The height of piles shall not exceed 20 feet. The width of piles shall not exceed 20 feet and the length 50 feet except that where the building is of noncombustible construction or is protected by automatic sprinklers the length of piles shall not be limited. In no case shall the ammonium nitrate be stacked closer than 36 inches below the roof or supporting and spreader beams overhead.
Aisles shall be provided to separate piles by a clear space of not less than 3 feet in width. At least one service or main aisle in the storage area shall be not less than 4 feet in width.
Related Code Sections
1910.109(i)(3) Hazardous Materials, Storage of Ammonium Nitrate in Bags, Drums, or Other Containers
Bags and containers used for ammonium nitrate must comply with specifications and standards required for use in interstate commerce (see 49 CFR ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.109 Explosives and Blasting Agents > 1910.109(i) Storage of Ammonium Nitrate > 1910.109(i)(3) Storage of Ammonium Nitrate in Bags, Drums, or Other Containers
1910.109(i)(3)(i)(b) Hazardous Materials,
Containers used on the premises in the actual manufacturing or processing need not comply with provisions of paragraph (i)(3)(i)(a) of this paragraph ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.109 Explosives and Blasting Agents > 1910.109(i) Storage of Ammonium Nitrate > 1910.109(i)(3) Storage of Ammonium Nitrate in Bags, Drums, or Other Containers > 1910.109(i)(3)(i) > 1910.109(i)(3)(i)(b)
1910.109(i)(3)(ii)(c) Hazardous Materials,
is of noncombustible construction or is protected by automatic sprinklers the length of piles shall not be limited. In no case shall the ammonium nitrate ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.109 Explosives and Blasting Agents > 1910.109(i) Storage of Ammonium Nitrate > 1910.109(i)(3) Storage of Ammonium Nitrate in Bags, Drums, or Other Containers > 1910.109(i)(3)(ii) > 1910.109(i)(3)(ii)(c)
1910.109(i)(3)(ii)(d) Hazardous Materials,
Aisles shall be provided to separate piles by a clear space of not less than 3 feet in width. At least one service or main aisle in the storage area ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.109 Explosives and Blasting Agents > 1910.109(i) Storage of Ammonium Nitrate > 1910.109(i)(3) Storage of Ammonium Nitrate in Bags, Drums, or Other Containers > 1910.109(i)(3)(ii) > 1910.109(i)(3)(ii)(d)
1910.109(i) Hazardous Materials, Storage of Ammonium Nitrate
Bags of ammonium nitrate shall not be stored within 30 inches of the storage building walls and partitions ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.109 Explosives and Blasting Agents > 1910.109(i) Storage of Ammonium Nitrate