• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

61.3.3 Storage of Aerosol Cooking Spray Products

Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products
JUMP TO FULL CODE CHAPTER

61.3.3.1 General

61.3.3.1.1

Aerosol cooking spray products shall be permitted to be stored in a general-purpose warehouse. [30B:6.3.1.1]

61.3.3.1.2

Aerosol cooking spray products shall be permitted to be stored mixed with other higher hazard aerosols as long as the provided isolation, storage height restrictions, and protection are based on the highest hazard aerosol product present. [30B:6.3.1.2]

61.3.3.2 Fire Protection

61.3.3.2.1

Encapsulated storage of cartoned aerosol cooking spray products shall be protected as uncartoned storage. [30B:6.3.2.1]

61.3.3.2.2

Stretch-wrapping of cartons of aerosol cooking spray products shall be protected as cartoned storage. [30B:6.3.2.2]

61.3.3.2.3

Wet-pipe automatic sprinkler protection shall be provided in accordance with Table 61.3.3.2.3(a) or Table 61.3.3.2.3(b) for cartoned aerosol cooking spray products stored in open frame racks without solid shelves or stored as palletized or solid pile storage. [30B:6.3.2.3]
Table 61.3.3.2.3(a) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (Metric Units)
Maximum Ceiling Height (m) Maximum Storage Height (m) Ceiling Sprinkler Protection Criteria Hose Stream Demand (L/min) Water Supply Duration (hr)
Sprinkler Type/Nominal Orifice (L/min/bar0.5) Response/Nominal Temperature Rating Design(# sprinklers @ discharge pressure)
9.1 7.6 ESFR-pendent K = 200 FR/Ordinary 12 @ 5.2 bar 950 1
[30B:Table 6.3.2.3(a)]
Table 61.3.3.2.3(b) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (English Units)
Maximum Ceiling Height (ft) Maximum Storage Height (ft) Ceiling Sprinkler Protection Criteria Hose Stream Demand (gpm) Water Supply Duration (hr)
Sprinkler Type/Nominal Orifice (gpm/psi0.5) Response/Nominal Temperature Rating Design (# sprinklers @ discharge pressure)
30 25 ESFR-pendent K= 14.0 FR/Ordinary 12 @ 75 psi 250 1
[30B:Table 6.3.2.3(b)]

61.3.3.2.4

Rack storage shall be arranged so that a minimum aisle width of 8 ft (2.4 m) is maintained between rows of racks and between racks and adjacent solid pile or palletized storage. [30B:6.3.2.4]

61.3.3.2.5

Solid pile and palletized storage shall be arranged so that no storage is more than 25 ft (7.6 m) from an aisle. Aisles shall be not less than 4 ft (1.2 m) wide. [30B:6.3.2.5]

61.3.3.2.6

Aerosol cooking spray product that is stored uncartoned shall be protected in accordance with Section 6.4 of NFPA 30B using the criteria for a Level 2 or Level 3 aerosol product, based on the product's chemical heat of combustion. [30B:6.3.2.6]

61.3.3.2.7

Protection criteria that are developed based on full-scale fire tests performed at an approved facility shall be considered an acceptable alternative to the protection criteria set forth in Table 61.3.3.2.3(a) or Table 61.3.3.2.3(b). [30B: 6.3.2.7]

61.3.3.2.8

Storage in occupancies other than warehouses or mercantile occupancies, such as in assembly, business, educational, industrial, and institutional occupancies, shall be permitted up to a maximum of 1000 lb (454 kg) net weight. [30B:6.3.2.8]

61.3.3.2.9

Solid pile, palletized, or rack storage of aerosol cooking spray product shall be permitted in a general-purpose warehouse that is either unsprinklered or not protected in accordance with this Code, up to a maximum of 2500 lb (1135 kg). [30B:6.3.2.9]

Related Code Sections


61.3.3 Aerosol Products, Storage of Aerosol Cooking Spray Products
] Encapsulated storage of cartoned aerosol cooking spray products shall be protected ...
Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products
61.3.3.2.1 Aerosol Products,
Encapsulated storage of cartoned aerosol cooking spray products shall be protected as uncartoned storage. [30B:6.3.2.1] ...
Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products > 61.3.3.2 Fire Protection > 61.3.3.2.1
61.3.3.2.2 Aerosol Products,
Stretch-wrapping of cartons of aerosol cooking spray products shall be protected as cartoned storage. [30B:6.3.2.2] ...
Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products > 61.3.3.2 Fire Protection > 61.3.3.2.2
61.3.3.2.9 Aerosol Products,
Solid pile, palletized, or rack storage of aerosol cooking spray product shall be permitted in a general-purpose warehouse that is either ...
Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products > 61.3.3.2 Fire Protection > 61.3.3.2.9
61.3.3.2.6 Aerosol Products,
Aerosol cooking spray product that is stored uncartoned shall be protected in accordance with Section 6.4 of NFPA 30B using the criteria for a Level ...
Fire Code 2018 of Maine > 61 Aerosol Products > 61.3 Storage in Warehouses and Storage Areas > 61.3.3 Storage of Aerosol Cooking Spray Products > 61.3.3.2 Fire Protection > 61.3.3.2.6
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING