• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section E4207 Storable Swimming Pools

Residential Code 2012 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools
JUMP TO FULL CODE CHAPTER

E4207.1 Pumps

A cord and plug-connected pool filter pump for use with storable pools shall incorporate an approved system of double insulation or its equivalent and shall be provided with means for grounding only the internal and nonaccessible noncurrent-carrying metal parts of the appliance.
The means for grounding shall be an equipment grounding conductor run with the power-supply conductors in a flexible cord that is properly terminated in a grounding-type attachment plug having a fixed grounding contact. Cord and plug-connected pool filter pumps shall be provided with a ground-fault circuit interrupter that is an integral part of the attachment plug or located in the power supply cord within 12 inches (305 mm) of the attachment plug.

E4207.2 Ground-Fault Circuit-Interrupters Required

Electrical equipment, including power-supply cords, used with storable pools shall be protected by ground-fault circuit-interrupters. All 125-volt, 15- and 20-ampere receptacles located within 20 feet (6096 mm) of the inside walls of a storable pool shall be protected by a ground-fault circuit interrupter. In determining these dimensions, the distance to be measured shall be the shortest path that the supply cord of an appliance connected to the receptacle would follow without passing through a floor, wall, ceiling, doorway with hinged or sliding door, window opening, or other effective permanent barrier.

E4207.3 Luminaires

Luminaires for storable pools shall not have exposed metal parts and shall be listed for the purpose as an assembly. In addition, luminaires for storable pools shall comply with the requirements of Section E4207.3.1 or E4207.3.2.

E4207.3.1 Within the Low-Voltage Contact Limit

A luminaire installed in or on the wall of a storable pool shall be part of a cord and plug-connected lighting assembly. The assembly shall:
  1. Have a luminaire lamp that is suitable for the use at the supplied voltage;
  2. Have an impact-resistant polymeric lens, luminaire body, and transformer enclosure;
  3. Have a transformer meeting the requirements of section E4206.1 with a primary rating not over 150 volts; and
  4. Have no exposed metal parts.

E4207.3.2 Over the Low-Voltage Contact Limit but Not Over 150 Volts

A lighting assembly without a transformer or power supply, and with the luminaire lamp(s) operating at over the low-voltage contact limit, but not over 150 volts, shall be permitted to be cord and plug-connected where the assembly is listed as an assembly for the purpose and complies with all of the following:
  1. It has an impact-resistant polymeric lens and luminaire body.
  2. A ground-fault circuit interrupter with open neutral conductor protection is provided as an integral part of the assembly.
  3. The luminaire lamp is permanently connected to the ground-fault circuit interrupter with open-neutral protection.
  4. It complies with the requirements of Section E4206.4.
  5. It has no exposed metal parts.

E4207.4 Receptacle Locations

Receptacles shall be located not less than 6 feet (1829 mm) from the inside walls of a pool. In determining these dimensions, the distance to be measured shall be the shortest path that the supply cord of an appliance connected to the receptacle would follow without passing through a floor, wall, ceiling, doorway with hinged or sliding door, window opening, or other effective permanent barrier.

Related Code Sections


Section E4207 Swimming Pools, Storable Swimming Pools
A cord and plug-connected pool filter pump for use with storable pools shall incorporate an approved system of double insulation or its equivalent ...
Residential Code 2012 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools
Section E4207 Swimming Pools, Storable Swimming Pools, Storable Spas, and Storable Hot Tubs
A cord and plug-connected pool filter pump for use with storable pools shall incorporate an approved system of double insulation or its equivalent ...
Residential Code 2018 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools, Storable Spas, and Storable Hot Tubs
E4207.3.2 Swimming Pools, Over the Low-Voltage Contact Limit but Not Over 150 Volts
A lighting assembly without a transformer or power supply, and with the luminaire lamp(s) operating at over the low-voltage contact limit ...
Residential Code 2012 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools > E4207.3 Luminaires > E4207.3.2 Over the Low-Voltage Contact Limit but Not Over 150 Volts
E4207.9 Swimming Pools, Pool Water Heaters
Electric pool water heaters shall comply with Section E4206.12 ...
Residential Code 2018 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools, Storable Spas, and Storable Hot Tubs > E4207.9 Pool Water Heaters
E4207.1 Swimming Pools, Pumps
A cord and plug-connected pool filter pump for use with storable pools shall incorporate an approved system of double insulation or its equivalent ...
Residential Code 2018 of South Holland > 42 Swimming Pools > E4207 Storable Swimming Pools, Storable Spas, and Storable Hot Tubs > E4207.1 Pumps
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING